8.8520.00.0
FlamQuench II
M
VENTING WITH FLAME AND PARTICLE RETENTION
INSTALLATION AND OPERATING INSTRUCTIONS
EXPLOSION PROTECTION SYSTEMS
Страница 1: ...8 8520 00 0 FlamQuench IIM VENTING WITH FLAME AND PARTICLE RETENTION INSTALLATION AND OPERATING INSTRUCTIONS EXPLOSION PROTECTION SYSTEMS ...
Страница 2: ... 2 2 7 IDENTIFICATION OF FLAMQUENCH II 2 3 INSTALLATION 2 4 SUPPORT CONSIDERATIONS 2 5 REFURBISHMENT INSTRUCTIONS 3 5 1 FILTER HANDLING WARNING 3 5 2 FILTER REPLACEMENT 3 5 2 1 REMOVE FILTER REFER TO FIGURES 4 AND 5 PAGES 11 AND 12 3 5 2 2 INSTALLATION OF FILTER S REFER TO FIGURE 6 PAGE 13 3 5 3 REFURBISH KITS 4 5 4 TOOLS NEEDED FOR REFURBISHMENT NOT INCLUDED AS PART OF KIT 4 6 SCHEDULED MAINTENAN...
Страница 3: ...bish Kits 4 Table 2 FlamQuench II English Specifications 6 Table 3 FlamQuench II Metric Specifications 7 Figure 1 Installation Diagram 8 Figure 2 Installation Orientation 9 Figure 3 FlamQuench II Specifications 10 Figure 4 FlamQuench II Assembly 11 Figure 5 FlamQuench II Assembly 12 Figure 6 Filter Installation 13 ...
Страница 4: ...ch II SAFETY WARNING Any damage to the Filter may cause the FlamQuench IIM to malfunction which may result in a dust explosion in the surrounding area 2 5 FlamQuench II INSTALLATION PROCEDURE WARNING When installing do not damage filter Any damage to filter may compromise the function of the FlamQuench IIM Refer to Figure 1 page 8 for assembly diagram Step 1 All system components shall be installe...
Страница 5: ...manently tagged The FlamQuench IIM has separate ID tags for each component See Figures 4 5 pages 11 12 for ID tag locations The ID tags contain the following information Size Part Number and Lot Number The explosion vent will be marked separately 3 INSTALLATION Keep a minimum distance of 2 feet 0 7 meters between the FlamQuench IIM and any equipment or walls to allow for proper venting FlamQuench ...
Страница 6: ... Be sure to note location of ID tag Refer to Figure 4 or 5 Step 3 Place Fiber Frax ring on top of Side Filter See Figure 6B page 13 Step 4 FlamQuench II sizes 8 20 DN200 DN500 skip to Step 9 Step 5 FlamQuench II sizes 24 40 DN600 DN1000 install Center Ring Support Weldment Refer to Figure 5 page 12 Step 6 Place Fiber Frax ring on top of Center Ring Support Weldment Step 7 Carefully install Side Fi...
Страница 7: ...e Kit Part Number English Kit Part Number Metric 8 DN200 E85 039 08 910020 12 DN300 E85 039 12 910021 14 DN350 E85 039 14 910022 16 DN400 E85 039 16 910023 20 DN500 E85 039 20 910024 24 DN600 E85 039 24 910025 30 DN750 E85 039 30 910026 DN800 Not Available 910027 36 DN900 E85 039 36 910027 40 DN1000 E85 039 40 910028 Note DN800 and DN900 FlamQuench II both use the same filter elements Table 1 Refu...
Страница 8: ...m Keep filter free of dust Use soft brush or vacuum to remove dust from filter Check for loose hardware The explosion vent is maintenance free 7 MAINTENANCE AFTER EACH FlamQuench II ACTIVATION Replacement is required after every activation This includes replacing filters and hardware See Section 5 page 3 8 EXPLOSION VENT REQUIREMENTS The following round Explosion Vents have been approved for use i...
Страница 9: ... 30 34 32 9 16 28 50 36 26 40 38 9 16 32 50 40 40 44 42 9 16 36 50 NOTE Flange stud torque values are based on using 1 8 Garlock 3600 gasket material and lightly oiled and freely running threads FQ II SIZE L W A WT LBS GASKET INSIDE DIA GASKET OUTSIDE DIA 8 23 13 1 44 8 1 8 10 5 8 12 26 19 1 80 12 3 16 15 3 16 14 31 22 2 113 14 3 16 17 3 16 16 35 25 2 168 16 19 20 37 28 2 199 20 23 24 57 32 2 402 ...
Страница 10: ...33 80 NOTE Flange stud torque values are based on using 1 8 Garlock 3600 gasket material and lightly oiled and freely running threads For burst pressures less or equal to 100 mbar at 22 C Use 33 N m otherwise 80 N m FQ II SIZE L W A WT KG GASKET INSIDE DIA GASKET OUTSIDE DIA DN200 597 330 44 20 208 268 Dn300 664 485 44 36 310 390 DN350 800 564 63 51 342 422 DN400 900 636 63 76 393 483 DN500 954 72...
Страница 11: ...Page 8 Manual P N 8 8520 00 0 Revision A October 15 2001 Figure 1 Installation Diagram FLAMQUENCH II LIFT RING EXPLOSION VENT ID TAG GASKET BOLTING PAD HARDWARE LIFT RING LIFT RING ...
Страница 12: ...Manual P N 8 8520 00 0 Page 9 Revision A October 15 2001 Figure 2 Installation Orientation FLAMQUENCH II SHALL BE MOUNTED WITHIN 90 OF VERTICAL SUPPORT TO BE EVALUATED CABLE SUPPORT ...
Страница 13: ...Page 10 Manual P N 8 8520 00 0 Revision A October 15 2001 Figure 3 FlamQuench II Specifications 8 40 DN200 DN1000 SIZES Ref Tables 2 and 3 ...
Страница 14: ...vision A October 15 2001 Figure 4 FlamQuench II Assembly Sizes 8 20 DN200 DN500 TOP FRAME WELDMENT ID TAG TOP OUTER FILTER ID TAG TOP INNER FILTER FIBER FRAX RING SIDE FILTER FIBER FRAX RING BOTTOM WELDMENT LOCK WASHER NUT BOLT ID TAG ...
Страница 15: ...40 DN600 DN1000 TOP FRAME WELDMENT TOP OUTER FILTER TOP INNER FILTER FIBER FRAX RING ID TAG ID TAG SIDE FILTER ID TAG FIBER FRAX RING CENTER RING SUPPORT WELDMENT FIBER FRAX RING SIDE FILTER BAND NUT FIBER FRAX RING LOCK WASHER BOLT BOTTOM WELDMENT BOLT NUT LOCK WASHER BOLT FLAT WASHER NYLON LOCK NUT ...
Страница 16: ...ion A October 15 2001 Figure 6 Filter Installation FIGURE 6A BOTTOM WELDMENT FIBER FRAX RING SIDE FILTER FIGURE 6B TOP OUTER FILTER ID TAG ID TAG TOP INNER FILTER FIBER FRAX RING SIDE FILTER TOP FRAME WELDMENT HARDWARE STAINLESS FIGURE 6C ...
Страница 17: ...olečnosti dochází k rozšíření portfolia a je navazována spolupráce s partnery v oblasti armatur komponent ventilů procesní měřící techniky a čerpadel Oblastí působnosti je potravinářský farmaceutický průmysl biotechnologie chemický průmysl petrochemie úprava vody papírenství a celulóza energetika keramický průmysl a zpracovatelský průmysl Firma REGOM INSTRUMENTS je díky širokému dodavatelskému por...
Страница 18: ...REGOM INSTRUMENTS s r o Brabcova 1159 2 147 00 Praha 4 CZECH REPUBLIC Tel 420 241 402 206 Fax 420 241 400 290 Mail regom regom cz Skype regom office www regom cz ...