BEFORE INSTALLING

This pull station must be installed in compliance with the control panel system 
installation manual, applicable NFPA standards, national and local Fire codes 
and the requirements of the AHJ (Authority Having Jurisdiction). Regular test-
ing of the devices should be done in accordance with the appropriate NFPA 
standards. Pull stations offer maximum performance when installed in com-
pliance with the National Fire Protection Association (NFPA); see NFPA 72.
NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The FIK-PULL-SA addressable pull station is a non-coded, single-action man-
ual pull station with a key-lock reset feature. It provides Fike intelligent fire 
alarm control panels (FACP) with one addressable alarm initiating input. The 
addressable module is housed inside the pull station. The FIK-PULL-SA is 
compatible with all Fike intelligent panels that use Fike IDP mode Refer to the 
FACP Installation Manual to determine if Fike IDP mode is supported. Operat-
ing instructions are molded into the pull station handle along with Braille text. 
Molded Terminal numbers are also present. 
The pull station meets the Americans with Disabilities Act Accessibility 
Guidelines (ADAAG) controls and operating mechanisms guidelines (section 
4.1.3[13]), the Americans with Disabilities Act (ADA) requirement for a 5 lb. 
maximum pull force to activate the pull station and conforms to ANSI/UL 
Standard 38.
Rotary dial switches are provided for setting the pull station’s address. (See 
Figure 3.) 

FIGURE 1. ADDRESSABLE MANUAL PULL STATION (SINGLE-ACTION)

 

R

 P0252-07

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Fike system control panel (list available from Fike).

MOUNTING AND SPACING

The FIK-PULL-SA Addressable pull station can be surface mounted to a SB-I/O 
surface backbox or semi-flush mounted on a standard single-gang, double-
gang or 4" (10.16 cm) square electrical box. The optional BG-TR trim ring can 
be used if the FIK-PULL-SA is to be semi-flush mounted.
For specific information regarding pull station placement refer to NFPA 72, 
ADAAG, and ADA.

SETTING THE ADDRESS

The FIK-PULL-SA Addressable pull station is factory preset with address ‘00.’ 
Set the address for the pull station by turning the rotary address switches on 
the addressable module mounted inside the pull station. Only one device per 
address is allowed. Multple modules may not be set to the same address on 
the Signaling Line Circuit. Once the address is set, record it in the space pro-
vided on the product ID label located inside the pull station. 

FIGURE 2. WIRING DIAGRAM

 

SLC

SLC

STRIP GAUGE

1     2     3     4

From 

FACP

To 

Next 

Addressable 

Device

P0267-00 

WARNING

Do not loop wiring under any terminals. Break wire run to maintain IDC su-
pervision.

SPECIFICATIONS

Normal Operating Voltage:  

24VDC.

Average Operating Current (LED Flash):   375 µA.
Maximum Operating Current (LED On):   5 mA.
Temperature Range:  

32°F – 120°F (0°C – 49°C).

Relative Humidity Range:  

10% - 93% non-condensing.

Dimensions: 

5.5" (139.7 mm) H x 4.1" (104.14 mm) W x 2.1" (53.34 mm) D

I56-6959-00

1

INSTALLATION AND MAINTENANCE INSTRUCTIONS

R

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

FIK-PULL-SA Addressable Pull Station 

(Single Action)

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

  

I56-6959-001 

 

 10/5/2021