FIK
-
IR3-HD
User Manual
Doc. No. 06-932.02
704 SW 10th St, Blue Springs, MO 64014, USA T: (+1) 816-229-3405
www.Fike.com
FIK-
IR3-HD Triple IR Flame Detector
Страница 1: ...FIK IR3 HD User Manual Doc No 06 932 02 704 SW 10th St Blue Springs MO 64014 USA T 1 816 229 3405 www Fike com FIK IR3 HD Triple IR Flame Detector...
Страница 2: ......
Страница 3: ...to use the specified equipment No part of this publication may be reproduced or transmitted for commercial purposes such as selling copies of this publication or for providing paid for support service...
Страница 4: ...4 Certification Instructions 4 2 5 Installing the Tilt Mount 4 2 6 Installing the detector 6 3 Configuration options 7 3 1 Sensitivity 7 3 2 Ultra Fast Detection 8 3 3 Alarm Delay 8 3 4 Alarm Latch 8...
Страница 5: ...6 2 Video functionality 18 6 3 Electrical Specifications 18 6 4 Outputs 18 6 5 Mechanical Specifications 19 6 6 Environmental Specifications 19 6 7 Label Figures 20 6 8 Approvals 21 6 9 Electromagneti...
Страница 6: ...ew 5 Figure 3 Detector on Tilt Mount Side View 6 Figure 4 Source 4 Wire Scheme 12 Figure 5 Sink 4 Wire Scheme 12 Figure 6 Source 3 Wire Scheme 13 Figure 7 Sink 3 Wire Scheme 13 Figure 8 RS 485 Network...
Страница 7: ...er provide additional means to study the cause and development of fire events 1 1 Key Features Extreme sensitivity up to 260ft 80m for a 1 ft2 0 1m2 N heptane pan fire 1 5 second detection time for 1...
Страница 8: ...ossible the detector face should be tilted aimed down at an angle to prevent the accumulation of dust and dirt Do not start an installation until the detector task definition system configuration inst...
Страница 9: ...f general purpose common tools and equipment Prior to installation Verify the appropriate purchase order Record the part and serial numbers of the detectors and the installation date and log Visually...
Страница 10: ...r example regular checks as part of routine inspections or establishing from the material s data sheet that it is resistant to specific chemicals 2 4 1 Specific conditions for use The equipment is not...
Страница 11: ...gnated location and secure it with four screws through four 0 28 7mm diameter holes There are four captive screws with spring washers in the tilt mount The following drawing shows the location of the...
Страница 12: ...les you to rotate the detector e Point the detector towards the detection area and make certain that the view of the area is unobstructed f Secure the detector in that position by tightening the locki...
Страница 13: ...ay Alarm latch Disabled Enabled Disabled Window heater Disabled Enabled Enabled Video module Disabled Enabled Enabled Post alarm video recording duration 1 2 or 3 minutes 1 minute Video analog output...
Страница 14: ...still detected the alarm outputs are activated 3 4 Alarm Latch If alarm latch is enabled the detector outputs will remain in alarm mode even after a flame is no longer detected To return the detector...
Страница 15: ...h a unique Modbus address The address of the detector can be set to any value in the range 1 247 3 8 Manual BIT Alarm Output Test When enabled the alarm outputs are activated when a Manual BIT is init...
Страница 16: ...support 800 979 FIKE 3453 10 4 Detector Wiring WARNING The sensor module in the front half of the detector contains no serviceable components and should never be opened The terminal compartment at the...
Страница 17: ...normally open SPST contact relay that is open in normal operation and closed when fire is detected This relay can be configured to latch as described in section 3 4 8 Alarm Relay COM 9 Analog Video C...
Страница 18: ...r 4 wire connected The following drawing shows how to wire the detector to act as a current source isolated transmitter 4 wire connection Figure 4 Source 4 Wire Scheme The following drawing shows how...
Страница 19: ...ability of the detector and communicator software it is possible to connect up to 32 detectors in an addressable system with 4 wires only 2 for power and 2 for communication Using repeaters the number...
Страница 20: ...FIK IR3 HD User Manual Doc No 06 932 02 For more information Technical support 800 979 FIKE 3453 14 Figure 8 RS 485 Networking...
Страница 21: ...3 To restart the detector turn off and then turn on the power 5 1 Output Signals The detector has the following output signals Current output 0 20mA Relays Fault and Alarm RS 485 Tri color LED Table 4...
Страница 22: ...tenance After powering up the detector should work maintenance free with the exception of optical window cleaning and an annual fire detection operational test WARNING The sensor module in the front h...
Страница 23: ...6 3 Yellow LED constantly on Fault Relay is open 0 20mA at 2mA BIT Fault Clean detector window Restart the detector by turning the power off and then back on Red LED constantly on Detector is in alar...
Страница 24: ...en Network Video Interface Forum Profile S 6 3 Electrical Specifications Operating Voltage 24 VDC nominal 18 32 VDC Current Consumption Standby 180mA Maximum 250mA all systems in operation including w...
Страница 25: ...on RS 485 Digital Video IP network IEEE 802 3 10 Base t 6 5 Mechanical Specifications Size 7 87 x 5 12 5 12 200 130 130mm Weight Detector Stainless Steel 316 9 8 lbs 4 4 kg Tilt mount Stainless steel...
Страница 26: ...FIK IR3 HD User Manual Doc No 06 932 02 For more information Technical support 800 979 FIKE 3453 20 6 7 Label Figures 6 7 1 Ex db...
Страница 27: ...C Ex db IIB T4 Gb 50 C Ta 85 C FM FMC Class I Div 1 Groups B C D T4 Class I Zone 1 AEx Ex db IIB T4 Gb T4 50 C Ta 85 C T5 50 C Ta 75 C Performance ANSI FM 3260 EN 54 10 6 9 Electromagnetic Compatibili...
Страница 28: ...r or replace it at its sole discretion if found to have been defective when shipped Said repair or replacement is FIRE GAS DETECTION TECHNOLOGIES INC s sole liability under this warranty and transferr...
Страница 29: ...ity Fuel Size Distance ft m Average Response Time Seconds N Heptane 1 x 1 ft 262 80 9 0 N Heptane 1 x 1 ft 230 70 4 1 N Heptane 1 x 1 ft 98 30 1 5 Gasoline 1 x 1 ft 230 70 3 6 Gasoline 2 x 2 ft 328 10...
Страница 30: ...32 plume 82 25 0 8 LPG 32 plume 98 30 1 4 Diesel 1 x 1 ft 79 24 3 9 JP5 1 x 1 ft 79 24 1 9 Kerosene 1 x 1 ft 79 24 2 5 Methanol 1 x 1 ft 75 23 1 2 Ethanol 1 x 1 ft 75 23 1 6 Isopropanol 1 x 1 ft 75 2...
Страница 31: ...modulated or non modulated False Stimuli at Extreme Sensitivity False Alarm Source Minimum Distance in ft m Sunlight Direct Reflected 2 0 6 Incandescent frosted glass light 300W 2 0 6 Fluorescent 70W...