68
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Fike IDP and SWIFT SLC Device Installation
Addressing IDP SLC Devices
7.5 Addressing IDP SLC Devices
All IDP devices are addressed using the two rotary dials that appear on the device board. Use the
ONES
rotary dial to set the ones place in a
one or two digit number, and use the
TENS
rotary dial to set the tens place in a two digit number.
IDPThe control panel recognizes when an IDP detector or IDP module is installed. For this reason, IDP detectors can be assigned any unique
address from 1 to 75, and IDP modules can be assigned any unique address from 1 to 5075. There can be an IDP detector using address 1 and
an IDP module using address 1. 0 is an invalid address.
Example 1:
To select device address 1, turn the
ONES
rotary dial to
1
and the
TENS
rotary dial to
0
as shown below.
Example 2:
To select device address 42, turn the
ONES
rotary dial to
2
and the
TENS
rotary dial to
4
as show below.
Figure 7.4 IDP SLC Device Addressing Using Rotary Dials
7.6 Wiring the FIK-W-WGI
For more information regarding gateway wiring instructions, see SWIFT manual LS10036-000FK-E.
7.6.1 SLC Connections
The FIK-W-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the FCP-75. It is powered
by the SLC loops or by a regulated, external 24 VDC UL listed power supply. For details about wireless devices, system setup, and opera-
tion, see the
SWIFT
Smart Wireless Integrated Fire Technology Instruction Manual P/N
LS10036-000FK-E.
NOTE:
Any device addressed over 75 will not be recognized by the panel.
Example 1: Device Set to 01.
Example 2: Device Set to 42.
All dials labeled for ONES
or TENS position.
NOTE 1:
The FIK-W-WGI, as part of the wireless network, has been tested for compliance with the Federal Communications Commission
(FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the USA is
subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may be
legally used outside the USA.
NOTE 2:
It is recommended to use the same wire gauge is there are multiple connections to the same terminal.