Network Management
Sync Network Options
•
eVance
•
UNUSED
Communicator Reporting Table
The Communicator Report Table specifies event reporting for each panel on the network. Each row in the table specifies a panel, event types
to report, primary and backup receiver numbers, and report by point or zone. Associated with the receivers are account number and daily test
option. The table can have up to 99 rows.
1.
From the Main Menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options Menu.
4.
Select 4 for Communicator Reporting Table.
5.
Press * to add rows, Press ENTER to edit data.
Figure 6.1 Communicator Reporting
6.3 Sync Network Options
After you make changes to network programming, if the distribution of network options fail, the system will report a trouble of network
options out of sync. Use this Menu to redistribute changed options to the rest of the network. The user will be required to choose a panel to
source the options from. Scroll down through the informational message and press ENTER to view the Select Source screen.
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 6 for Network Programming Menu.
3.
Select 8 for Sync Network Options.
4.
Select which panel to source the options from.
Figure 6.2 SYNC Network Options
Panel#
0=Delete
Primary Receiver
Number
Test Primary Account
Secondary Receiver
Number
Test Secondary Account
Report Alarms
Report Supervisory
Report Troubles
Report Event by Point
Y=Point/N=Zone
Panel: 03 YYYY
R009:321456 N
R013:987456 N
<Help Text>
P#ASTP Prit Sect
01=03YYYY 009N 013N
02=02NNYN 015N 014Y
* = Add Row
With the line selected
Scroll down to show checksum
Line 1 scrolls to show the date