Installing the FIK-125W
Device Installation
4.6.2 Mounting the FIK-125W
The FIK-125W is equipped with a separate enclosure. Refer to Section 3.1 when selecting a mounting location for the FIK-125W.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the center of the building as possible and located
within a secured area, but should be accessible for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on concrete, especially when moisture is
expected, attach a piece of 3/4-inch plywood to the concrete surface and then attach the cabinet to the plywood. Also mount any other mod-
ules to the plywood.
The cabinet can be surface or flush-mounted. If you will be flush-mounting the cabinet, the hole for the enclosure should be 14.5" W x
24.75" H x 3-7/16” D (36.8cm W x 62.9cm H x 8.73cm D). Do not flush-mount in a wall designated as a fire break. The Outside dimensions
of the cabinet are 16" W x 26-1/4” H x 4-1/8” D (40.64cm W x 66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1.
On the mounting surface install two screws level with each other 11" apart.
Figure 4.30 Cabinet Flush Mount Dimensions and Mounting Hole Locations
2.
Install the cabinet onto the two mounting screws and tighten the screws.
3.
Insert two screws into the two bottom mounting holes.
4.6.3 Mounting the FIK-125WBD Board Only
1.
Make certain that AC and DC power have been removed from the panel.
2.
If this module is a replacement for an existing FIK-125W, remove the screws which secure the board to the enclosure.
Key Holes
Board mounting
bracket
Bottom mounting
holes
NOTE:
Installation and wiring of this device must be done in accordance with NFPA 72 and local ordinance