D500-73-00 

I56-2462-02

704 South 10th Street, Blue Springs, MO 64015 

(816) 229-3405

www.fike.com

INSTALLATION INSTRUCTIONS

55-043 Relay Module

SPECIFICATIONS

Normal Operating Voltage: 

15 to 30 VDC

Standby Current: 

500 

µ

A max. average (continuous broadcasts)

Alarm Current: 

2.0 mA (red LED on)

Short Circuit Current
 

Dry Control Input: 

30 µA max. Avg. (5 VDC)

Maximum Resistance
 

Dry Contact Input: 

100 

Ω

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% RH Noncondensing

Dimensions: 

4.17

ʺ

×

 4.26

ʺ

×

 1.22

ʺ

D

 

 

(106mm H 

×

 108mm W 

×

 31mm D)

Accessories: 

Wall cover plate (included)

 

 

SMB500 Surface Mount Electrical Box

 

 

EA-CB Control Module Barrier

BEFORE INSTALLING

This  information  is  included  as  a  quick  reference  installation 
guide. Refer to the appropriate control panel installation manual 
for detailed system information. If the modules will be installed 
in an existing operational system, inform the operator and local 
authority that the system will be temporarily out of service.

NOTICE:

 This manual should be left with the owner/user of this 

equipment.

GENERAL DESCRIPTION

Relay  Module,  Model  55-043,  is  to  be  designed  for  use  in  acti-
vation  of  the  types  of  products  that  are  generally  connected  to 
an  intelligent  fire  alarm  system.  It  provides  two  sets  of  form  C 
contacts that switch together (one DPDT relay). There is also an 
input that is capable of monitoring a dry set of contacts for open 
or closed conditions.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a 
listed compatible control panel.

LED

INDICAT OR

IR 

RECEIVER

C0166-00

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3A

30 VDC

RESISTIVE

NON-CODED

2A

30 VDC

RESISTIVE

CODED

1A

30 VDC

INDUCTIVE (L/R = 2 ms)

CODED

0.5A

30 VDC

INDUCTIVE (L/R = 5 ms)

CODED

0.9A

70.7 VAC

RESISTIVE

NON-CODED

0.7A

70.7 VAC

INDUCTIVE (PF = 0.35)

NON-CODED

NOTE:

  This module is not approved for use in the European Union, at or above 50VAC or 70VDC.

MOUNTING

The module mounts directly to 4

ʺ

 square electrical boxes. The box 

must have a minimum depth of 2

1

8

ʺ

. Modules must be mounted 

with the arrow facing upward for proper operation of the IR pro-
gramming  tool.  Surface  mounted  electrical  boxes  (SMB500)  are 
available from Fike.