INSTALLATION AND MAINTENANCE INSTRUCTIONS

55-042 Supervised Control Module

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to the 
appropriate control panel installation manual for detailed system information. 
If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

Control Module, Model 55-042, is used to switch an external power supply 
or audio amplifier to notification appliances. In addition to switching the ex-
ternal power, the device will monitor the wiring (while external power is not 
switched to the auxiliary devices) to the auxiliary device for open and short 
circuits via an end of line resistor. This module is capable of Class A or Class 
B operation. 

The control module will also have the capability to monitor the external 
power input for loss of power (DC voltage supplies only). This feature can 
be disabled through device configuration programming. If the external power 
is switched to the auxiliary devices and there is a loss of the DC supply, the 
control module has the capability of running an algorithm in which the device 
will switch back to monitor mode and check the line for short circuits. If no 
short exists, the device will reapply the external power. This algorithm can 
be enabled when using a DC external supply that is guaranteed to be above 
9 volts.

SPECIFICATIONS

Normal Operating Voltage: 

15 to 30 VDC

Standby Current: 

630 µA maximum average (continuous broadcasts)

Alarm Current: 

2 mA (red LED on)

Maximum NAC Circuit Line Loss:  4 VDC
Power Supply Monitor
 

Maximum (Speakers): 

70.7 Vrms, 50W

 

Maximum (NAC): 

Regulated 24 VDC

 

Trouble Range: 

0 to 2 VDC

Maximum NAC Current Ratings: 

For Class B Wiring Systems, 3A; For Class A Wiring Systems, 2A

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10% to 93% RH Non-condensing

Dimensions: 

 4.675˝ H x 4.275˝ W x 1.4˝ D

Accessories: 

 39  k

Ω

 End of Line Resistor Part # A2263-00 (included); Wall cover plate (included); SMB500 Surface Mount Electrical Box; 

A2143-60 Bypass capacitor; EA-CB Control Module Barrier

I56-2463-008

 704 S. 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277

R

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a listed compat-
ible control panel.

MOUNTING

The module mounts directly to 4-inch square electrical boxes. The box must 
have a minimum depth of 2

1

/

8

 inches. Modules must be mounted with the ar-

row facing upward for proper operation of the IR programming tool. Surface 
mounted electrical boxes (SMB500) are available from Fike.

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations. 

1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams. Optional EA-CB may be required to separate power 
limited and non power limited wiring in the electrical box.

2.   For new installations use the enclosed 39 k

Ω

 EOL resistor. For retrofit ap-

plications where the existing 47 k

Ω

 cannot be easily replaced, it may be 

left in place without loss of performance.

3.   Set the address on the module per job drawings using the handheld IR 

programmer.

4.  Secure module to electrical box (supplied by installer). 

NOTE:  All references to power limited represent “Power Limited (Class 2)”. 

All references to Class A also include Class X.

RELAY CONTACT RATINGS:

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

2 A

25 VAC

PF = 0.35

Non-coded

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

0.46 A

30 VDC

(L/R = 20ms) 

Non-coded

0.7 A

70.7 VAC

PF = 0.35

Non-coded

0.9 A

125 VDC

Resistive

Non-coded

0.5 A

125 VAC

PF = 0.75

Non-coded

0.3 A

125 VAC

PF = 0.35

Non-coded

Содержание 55-042

Страница 1: ...ted 24 VDC Trouble Range 0 to 2 VDC Maximum NAC Current Ratings For Class B Wiring Systems 3A For Class A Wiring Systems 2A Temperature Range 32 F to 120 F 0 C to 49 C Humidity 10 to 93 RH Non condensing Dimensions 4 675 H x 4 275 W x 1 4 D Accessories 39 kΩ End of Line Resistor Part A2263 00 included Wall cover plate included SMB500 Surface Mount Electrical Box A2143 60 Bypass capacitor EA CB Con...

Страница 2: ...te during shipping To ensure that the switch contacts are in their correct state modules must be made to com municate with the panel before connecting circuits controlled by the module TERMINAL DEFINITIONS T1 SLC in out T9 External Power Line in out T2 SLC in out T10 External Power Line in out T3 SLC in out T11 NAC A B T4 SLC in out T12 NAC A B T7 External Power Line in out T13 Class A T8 External...

Страница 3: ...FOR FIRE PROTECTION WITH BATTERY BACK UP ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED FIGURE 3 TYPICAL CLASS A STYLE Z NAC CONFIGURATION TO NEXT DEVICE FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT SLC 30 VDC MAX TWISTED PAIR RECOMMENDED EOL RESISTOR IS INTERNAL AT TERMINALS 13 14 UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL A77 716B OR EQUIVALENT REQUIRED FOR PANELS WITHOUT POWER SUPPL...

Страница 4: ...e equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help FIGURE 4 TYPICAL CLASS B STYLE Y AUDIO NAC CONFIGURATION TO NEXT DEVICE FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT SLC 30 VDC MAX TWISTED PAIR RECOMMENDED EOL RESISTOR SPEAKERS MUST BE LISTED FOR F...

Отзывы: