26-1029 Issue 6 

 

 

 
 

General Description 

 

The Sita Sounder/Strobe unit allows for audible and visual indication when 
the system enters an alarm condition. This is an addressable unit that 
attaches to the loop. Digital communication technology to the control panel is 
implemented allowing for accurate data transfer at high transmission speeds. 
This device is only compatible with the Sita 200+, Duonet and Quadnet 
ranges of control panels. 

 

Before Installation 

 

The Sounder/Strobe must be installed in compliance with the control panel installation manual. The installation must 
also meet the requirements of any local authority. For maximum performance the device  should be installed in 
compliance with BS 5839. Pt1 : 2002 + A2 : 2008. 

 

Spacing 
 

Fike  recommends spacing of sounders/strobes  in accordance with BS  5839.  For more specific information 
regarding sounder spacing, placement and special applications please refer to BS 5839 Pt1 : 2002 + A2 : 2008. 
 

Device Installation 
 

The base moulding should be positioned so that access to the locking screw is concealed from general view to 
lessen the possibility of unauthorised removal of the device. 
 
Drill the cable entry region(s) in base moulding as required. 
 
Drill out the desired mounting holes through hole / slot guides as required. Affix the base moulding to a flat surface 
using a minimum of 2 screws. 

 

 All wiring must be installed in compliance with the recommendations laid out by BS 5839 as well as any special 
recommendations documented in the control panel installation manual. 

The cabling used should be of a 2-core 

1.5mm

2

 screened, fire resistant type, with the following characteristics: 

 

 
Max Capacitance Core to Screen ................................................... 180pF / m 
Max Capacitance Core to Core....................................................... 100pF / m 
Max Inductance ............................................................................... 1.0mH / km 
Max Resistance Two Core Screened 1.5mm² ................................ 

12.1Ω / km 

 
It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on 
this system is not permitted.

  Cables may be terminated into the connector, as shown below. Care should be 

taken when terminating devices to ensure all cables are correctly sleeved and connections are secure. Improper 
connections will prevent a system from responding properly in the event of a fire. 
 

 

Terminal 

Description 

 

L1 

Loop +ve IN 

 

0V 

Loop -ve IN 

 

SCRN 

Screen IN 

 

SCRN 

Screen OUT 

 

0V 

Loop -ve OUT  

 

L2 

Loop +ve OUT 

 

 

 
 

 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 
 
 

326-0023 Sita Sounder/Strobe  
with Deep Base 

 