General Description 

 

The Sita Hipoint unit allows for audible indication when the system enters an alarm 
condition. This is an addressable unit that attaches to the loop. Digital communication 
technology to the control panel is implemented allowing for accurate data transfer at 
high transmission speeds. This device is only compatible with the Sita200plus, 
Duonet and Quadnet ranges of control panels. 

 

Before Installation 

 

The Sounder must be installed in compliance with the control panel installation 
manual. The installation must also meet the requirements of any local authority. For 
maximum performance the sounder should be installed in compliance with 
BS5839 Pt1 : 2002 + A2 : 2008. 

 

Spacing 

 

Fike recommends spacing of sounders in accordance with BS5839 Pt1. For more specific information regarding 
sounder spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 
 

Device Installation 

 

Fix the back box in a suitable position using at least two screw holes/slots, remembering to allow enough cable 
length for installation. All wiring must be installed in compliance with the recommendations laid out by BS 5839 as 
well as any special recommendations documented in the control panel installation manual.  
 

The cabling used should  be of a 2-core 1.5mm

2

  screened, fire resistant type, with the following 

characteristics: 

 

 
Max Capacitance Core to Screen ................................................... 180pF / m 
Max Capacitance Core to Core....................................................... 100pF / m 
Max Inductance ............................................................................... 1.0mH / km 
Max Resistance Two Core Screened 1.5mm² ................................ 

12.1Ω / km 

 
It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on 
this system is not permitted.

  

 
Cables may be terminated into the connectors, as shown below. No  screen connection is allowed for within the 
device. Incoming and outgoing cable screens must therefore be connected through using a suitable connector. The 
cable screens must not be connected to building earth. Care should be taken when terminating devices to ensure 
all cables are correctly sleeved and connections are secure. Improper connections will prevent a system from 
responding properly in the event of a fire. 
 

 
 

Terminal 

Description 

 

+VE IN 

Loop +ve IN 

 

0V IN 

Loop -ve IN 

 

0V OUT 

Loop -ve OUT 

 

+VE OUT 

Loop +ve OUT 

 

 

 
 
The  Loop +ve (positive) IN  and the Loop +ve (positive) OUT  connections are split within the module, for cable 
continuity readings at the commissioning stage they must be temporarily removed and connected through. Please 
remember that all high voltage testing must be carried out before the installation of the electronics, otherwise the 
electronics will be damaged. Please also remember to use a suitable connection (not supplied) to maintain the 
screen integrity of the loop. 

 

 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 
 

323-0001 Sita Hipoint 

+

V

E

 O

U

T

0

V

 IN

+

V

E

 IN

0

V

 O

U

T