26-0874 Issue 10 

 

 

 
 

 

General Description 

 

The Multipoint ASD is a plug-in type smoke detector that utilises a photo-electric 
sensing chamber to make a measurement corresponding to smoke density. The 
device also incorporates a thermistor sensing circuit to allow for accurate heat 
measurement. These elements allow the device to be configured to a smoke, heat 
or combined setting. Digital communication technology to the control panel is 
implemented allowing for accurate data transfer at high transmission speeds. This 
device is only compatible with the Sita200plus, Duonet and Quadnet ranges of 
control panels and may also incorporate a sounder or visual indication beacon 
(ignore all references to sounders/beacons if your device has no sounder/beacon).  

 

Before Installation 

 

The detector must be installed in compliance with the control panel installation manual. The installation must also 
meet the requirements of any local authority. For maximum performance the detector should be installed in 
compliance with BS5839 Pt1 : 2002 + A2 : 2008. 

 

Spacing 
 

Fike recommends spacing detectors in accordance with BS5839 Pt1. Due to the effects of IR and possible 
magnetic interference, detectors should not be fitted any closer than 500mm (preferably 1000mm) to a light fitting or 
any other source  of  IR  or EMI. In addition to this recommendation,  the device should be mounted so that the 
indication  LED is facing towards the light source. For more specific information regarding detector spacing, 
placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 
 

Detector Installation 
 

All wiring must be installed in compliance with the recommendations  laid out by BS5839 as well as any special 
recommendations documented in the control panel installation manual. 

The cabling used should be of a 2-core 

1.5mm

2

 screened, fire resistant type with the following characteristics: 

 

 
Max Capacitance Core to Screen ................................................... 180pF / m 
Max Capacitance Core to Core....................................................... 100pF / m 
Max Inductance ............................................................................... 1.0mH / km 
Max Resistance Two Core Screened 1.5mm² ................................ 

12.1Ω / km 

 
It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on 
this system is not permitted.

  Cables may be terminated into the connectors mounted in the base, as shown 

below. Care should be taken when terminating devices to ensure all cables are correctly sleeved and connections 
are secure. Improper connections will prevent a system from responding properly in the event of a fire. 
 
 

Terminal 

Description 

 

1  /  LOOP 0V 

Loop –ve IN & OUT 

(also Remote LED 0V if used) 

2  /  LOOP +IN 

Loop +ve IN 

 

3  /  LOOP +OUT 

Loop +ve OUT 

 

4  /  AUX +VE 

Auxve if used 

(or Remote LED +ve if used) 

5  /  AUX –VE 

Auxiliary –ve if used

 

 

SCRN 

Cable Screen 

 

 
 
The  Loop  +ve (positive) IN and the Loop +ve (positive) OUT  connections  are automatically joined together (short 
circuit)  by a  spring  arm between terminals 2 and 3 until the detector is installed. This allows  for  cable continuity 
readings at the commissioning stage.  

 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 
 
 

205-0003 Sita Multipoint ASD Detector, 
205-0001 Sita Multipoint ASD with Sounder,  
205-0012 Sita Multipoint ASD with Sounder / Strobe  


 


 


 


 


 


 


 


 


 