Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-24 ControlNet
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version:
1.06
Document Revision: 7
Страница 1: ...iver Manual Supplement to the FieldServer Instruction Manual FS 8700 24 ControlNet APPLICABILITY EFFECTIVITY Effective for all systems manufactured after May 1 2001 Driver Version 1 06 Document Revision 7 ...
Страница 2: ...ver Side Connection Descriptors 7 4 2 ControlNet Node Descriptors 8 4 3 Unscheduled Map Descriptors using PCCC messaging 8 4 3 1 FieldServer Specific Map Descriptor Parameters 8 4 3 2 Driver Specific Map Descriptor Parameters 9 4 3 3 Timing Parameters 9 4 3 4 Unscheduled Map Descriptor Example 10 Appendix A Advanced Topics 11 Appendix A 1 Write throughs 11 Appendix A 2 Map Descriptor functions 11 ...
Страница 3: ...dded in the ControlNet messages When the FieldServer originates PCCC messages to communicate with PLC5 controllers it uses connected messages This provides fast reliable communication to the other node When another device originates PCCC messaging the FieldServer will emulate a PLC5 controller supporting connected or unconnected messages to files N7 through to N32 FieldServer Technologies 1991 Tar...
Страница 4: ... BNC Tee Connector ControlNet Tools CD ControlNet Module User s Guide Version 1 00 CNF2BSS EXE utility FS 8700 24 Driver Manual 2 2 Provided by the Supplier of 3rd Party Equipment PART DESCRIPTION ControlNet Network with cables and terminators FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldServer com Tel 408 262 2299 Fax 408 262 9042 Toll_Free 888 509 1970 ema...
Страница 5: ...M A port A 75 ohm terminator must be placed at either end of the ControlNet Bus BASE NAME FILE NAME FS8700 24 FIELDSERVER CONTROLNET CONNECTION DIAGRAM DATE 11 4 05 BY MC 408 262 2299 FS x40 SST 5136 CN ISA A B To ControlNet Network 75 O network terminators 75 O T pieces FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldServer com Tel 408 262 2299 Fax 408 262 904...
Страница 6: ...erver is set to the System_Station_Address specified in the FieldServer configuration file Section Title Bridge Column Title Function Legal Values System_Station_Address Provide MacId for the FieldServer 1 99 Example Bridge Information Bridge System_Station_Address 5 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldServer com Tel 408 262 2299 Fax 408 262 9042 To...
Страница 7: ... its interfaces and the routing of data required In order to enable the FieldServer for ControlNet communications the driver independent FieldServer buffers need to be declared in the Data Arrays section the FieldServer virtual node s needs to be declared in the Nodes section and the data to be transferred needs to be mapped in the Unscheduled Map Descriptors section Details on how to do this can ...
Страница 8: ... Map Descriptors using PCCC messaging Maintained on the SST 5136 CN ISA card are 32 integer files N7 N39 that can be read or written to by other devices on the ControlNet network using PCCC messaging Client style Map Descriptors are used to transfer data to or from the file buffers on the card to the Data Arrays on the FieldServer 4 3 1 FieldServer Specific Map Descriptor Parameters Column Title F...
Страница 9: ...ess within file 0 999 INT SINT 0 499 REAL FLOAT 0 15999 BOOL BIT FLAG Length Length of Map Descriptor 1 249 INT SINT 1 124 REAL FLOAT 1 3984 BOOL BIT FLAG Note the number of bytes per PCCC_Type SINT INT 2 bytes REAL FLOAT 4 bytes BOOL BIT FLAG 8 bits per byte Each PLC file is 2000 bytes long and therefore the address values will range from zero to a maximum value as indicated The start address is ...
Страница 10: ...riptor will send data to the card to allow other nodes to read the data contained in the FieldServer s Data Array Server Side Map Descriptors Map Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Block_Number PCCC_Type Length Address A1 DA_AI3 0 WRBC Local 7 SINT 5 125 Offset into the file Offset into the file N7 33 N7 125 Active Map Descriptor polls the PLC regu...
Страница 11: ...ptors Note that WRBC Map Descriptors write data from the FieldServer s Data Arrays into the output data memory area of the card whereas RDBC Map Descriptors place data from the card s input data memory area into the FieldServer s Data Arrays The IO data memory areas are kept in RAM on the card and are defined by Connection Control Blocks on the card Data Array WRBC Mapdesc Data Array RDBC Mapdesc ...
Страница 12: ...al Page 12 of 12 THIS PAGE INTENTIONALLY LEFT BLANK FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldServer com Tel 408 262 2299 Fax 408 262 9042 Toll_Free 888 509 1970 email support fieldServer com ...