Quick Start

1. Power on your SRH3 by holding the 

ON/OFF button for 1 second. 

2.  Use the TSH/TEET/NORM button to  

select NORMAL mode.

3.  Press the RH/DP/WB button to cycle 

between relative humidity, dew 

point, and wet bulb temperatures.

4. The air temperature will always be 

shown in the lower display and the 

relative humidity, dew point, or wet 

bulb measurement will be displayed 

in the upper display in real-time.

5. Insert sensor probe into duct for 

in-duct measurements.

 

Certifications

   C-Tick (N22675)

   CE 

  

WEEE

    

     

RoHS Compliant

Description

With your purchase of the SRH3 you 

now have the ability to take supply/

return temperature, %RH, wet bulb 

and dew point measurements from 

inside the duct or plenum.

Your SRH3 is a portable, hand held, 

diagnostic psychrometer, designed 

for the HVAC/R technician.

SRH3 helps you properly charge 

a fixed restrictor system by quickly 

determining the Target Superheat 

(TSH). Your SRH3 can also help 

determine optimum airflow across 

the evaporator by easily performing 

a Target Evaporator Exit Temperature 

(TEET) test.

The 38"(96cm) telescoping probe 

with laser etched ruling and flattened 

edges allows you to locate proper 

measurement points within a duct and 

ensures that your probe is properly 

aligned. 

The dual display with a bright 

backlight, rugged rubber boot with 

probe clips, make sure the SRH3 is 

ready for any job.

Display

      

Auto Power Off Enabled 

     

Low Battery Indicator

     

Relative Humidity 

 

   

Dew Point

     

Wet Bulb  

 

      

Dry Bulb

     

%Relative Humidity

    

Outdoor

    

Indoor

     

Target Superheat 

 

   

Target Evaporator Exit Tem- 

  

perature

     

Normal Range

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

  

Temperature (Fahrenheit)

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

  

Temperature (Celsius)    

      

Hold Display

      

Maximum Display

      

Minimum Display

Fieldpiece

In-Duct 

Problem-Solving 

Psychrometer

OPERATOR'S  

MANUAL

Model SRH3

 

Controls

   

Hold 1 second to toggle power on/off.

   

Toggle Backlight. (Hold while powering  

 

your SRH3 on to disable APO.)

   

 

Toggle display to show relative  

 

 

humidiy, dew point and wet

   

 

bulb  temperatures

  

   

Toggle between Fahrenheit and Celcius.  

 

Hold for 2 seconds to display battery  

 percentage.

   

Toggles to display Maximum, Minimum,  

 

or Hold the current reading. Hold for 1  

 

second to exit and clear stored values.

   

Confirm Selection

   

Outputs calculations for Target    

 

Superheat or Target Evaporator Exit  

 Temperature

   

 

Toggle to enter Target Superheat,  

 

 

Target Evaporator Exit Temp, or  

 

 

Normal modes.

Functions

Backlight

1.   Press the backlight button to toggle the backlight 

on/off at any time during the SRH3's use. 

Note: The back light will automatically shut off after 1 

minute to conserve battery life.

Maximum/Minimum/Hold

1.   Pressing the MAX/MIN/H button activates the 

Max-Min-Hold function, holding the maximum and 

minimum measured values until cleared.

2.  Once the Max-Min-Hold function has been 

enabled, pressing MAX/MIN/H cycles between 

displaying maximum (MAX), minimum (MIN) and 

freezing the current value.

3. Press and hold the MAX/MIN/H button for 2 seconds 

to erases all stored maximum and minimum values 

and return to real-time measurements.

Units

1.  Press the units button to switch between degrees 

Fahrenheit and Celsius.

Battery Check

1. Press and hold the UNIT button for 2 seconds to 

display the battery life in percentage.

Output

1.  Press the OUTPUT button to perform calculations 

of Target Superheat and Target Evaporator Exit 

Temperature after necessary measurements have 

been entered.

How to Use

Normal Mode

Normal mode allows you quickly 

and easily take real-time dry bulb, wet 

bulb, dew point, and relative humidity 

measurements.

1. Press TSH/TEET/NORM button until NORM is 

displayed in lower left corner.

2. For upper display measurements, press the RH/DP/

WB button to toggle relative humidity, dew point, 

or wet bulb temperature measurements.

Note:  Dry bulb (air temperature) will always show in 

the lower display.

Target Superheat Mode

Perform a simple Target Superheat 

test to determine what the superheat 

should be on a fixed restrictor system. 

Use the target superheat to compare 

to the actual superheat to determine 

if a system is properly charged.

1. Press TSH/TEET/NORM button until TSH is displayed 

in the lower left of the LCD.

2. Take a wet bulb measurement at the inlet of the 

evaporator. Generally right before the filter is a 

good location. Drill or punch a 3/8" hole into the 

return plenum for a measurment depth of up to 

24 inches. See Figure 1 for recommended return 

plenum placement of probe. Insert SRH3 probe into 

the plenum to take the wet bulb measurement. 

Press ENTER to lock in the reading. 

3. Take a dry bulb (air temperature) measurement 

going into the condensor. Press ENTER to lock in 

the reading.

4. Press OUTPUT to calculate the target superheat. 

Compare the target superheat to the actual 

superheat of the system.

5. Seal any holes before leaving the jobsite.

Target Evaporator Exit 

Temperature Mode

Target Evaporator Exit Temperature  

(TEET), aka temperature drop or 

delta T, is used to determine if the 

evaporator is getting the optimum 

airflow. A TEET test can be quickly 

performed by taking two easy 

temperature measurements at the 

return side of the evaporator.

1. Press the TSH/TEET/NORM button until TEET is 

displayed in the lower left of the LCD.

2. Take a wet bulb measurement inside the return 

plenum. Drill or punch a 3/8" hole into the return 

plenum. See Figure 1 for recommended return 

plenum placement of probe. Insert SRH3 probe into 

the plenum to take the wet bulb measurement. 

Press ENTER to lock in the reading.

3. Take a dry bulb measurement at the same place the 

previous wet bulb measurement was taken. Press 

ENTER to lock in the reading.

4. Press OUTPUT to calculate the target evaporator exit 

temperature. Compare this calculated target to the 

actual evaporator exit temperature.

5. Take a dry bulb measurement inside the supply 

plenum to check the actual Evaporator Exit 

Temperature. See Figure 1 for recommended supply 

plenum placement of probe. Drill or punch a 3/8" 

hole into the supply plenum. Press TSH/TEET/NORM 

until NORM is displayed.Insert SRH3 probe into 

the plenum and read the temperature in the lower 

display.

6. Seal any holes before leaving the jobsite.

Note:  For both Target Superheat and Target Evaporator 

Exit Temperature modes, you can adjust any 

temperature measurement after calculations have 

been performed by pressing ENTER. This prompts 

you to re-take the measurements.

RCONE1 Probe Lock

Use the RCONE1 to lock your sensor 

probe in place inside the duct. Using 

the RCONE1 and magnet on the SRH3 

allows you hands-free in-duct testing. 

See Figure 2.

Specifications

Telescoping Probe Length: Up to 38 inches (97cm)

Probe Tip Diameter: 0.35 inch (9mm)

Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 

to 80% RH (with battery removed)

Temperature Coefficient: 0.1 x (specified accuracy)/°C 

(<18°C or >28°C)

Over range:

  

"OL" or "-OL" is displayed

Power: Single standard 9-volt battery, NEDA 1604, JIS 

006P, IEC 6F22 

Auto Power off:

 

after 15 minutes of inactivity if APO 

is active.

Battery life: 150 hours typical (alkaline)

Low Battery Indication:    is displayed when the 

battery voltage drops below the operating level.

Dimensions: 7.9 in (H) x 2.6 in (W) x 1.4 in (D), 

[200mm (H) x 66mm (W) x 36mm (D)]

Weight:  Approx. 400g, including battery

Temperature:

Sensor type: Precision thermistor

Operating environment:  -4°F to 140°F (-20°C to 60°C)

Range: -4°F to 140°F (-20°C to 60°C)

Resolution: 0.1°F / 0.1°C

Accuracy:   ±(1°F) 32°F to 113°F

   

±(2°F) -4°F to 32°F, 113°F to 140°F

   

±(0.5°C) 0°C to 45°C

   

±(1°C) -20°C to 0°C, 45°C to 60°C

Relative Humidity:

Sensor Type: Capacitance polymer film

Operating environment: 32°F to 131°F (0°C to 55°C)

Range: 0% to 100%RH

Accuracy:   ±(2.5%) 10% to 90%RH 

   

±(5%) <10%RH and >90%RH

  Note: Above accuracies stated at 73.4°F (23°C).

Sensor Response Time: 60 seconds typical for 90% of 

total range.

Sensor Hystersis: ±1%RH typical (Excursion of 10% to 

90% to 10%RH)

80

SRH3

PRESS 1 SEC

TO CLEAR

PRESS FOR

1 SECOND

In-Duct

Diagnostic

Psychrometer

UNITS

ON/OFF

TSH/TEET/NORM

RH/DP/WB

AUTO-OFF

BATTERY

CHECK

ENTER

MAX/MIN/H

OUTPUT

80

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

80

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

RH/DP/WB

UNITS

BATTERY

CHECK

PRESS 1 SEC

TO CLEAR

MAX/MIN/H

ENTER

OUTPUT

TSH/TEET/NORM

ON/OFF

Recommended Hole

Placement for Supply

Plenum Measurements

Recommended

Hole Placement for

Return Plenum

Measurement is

directly before the

evaporator coil. Look behind

the panel before drilling and make

sure you do NOT drill a hole through any critical HVAC compo-

nents. 

Figure 1

SRH3

PRESS 1 SEC

TO CLEAR

PRESS FOR

1 SECOND

In-Duct

Diagnostic

Psychrometer

UNITS

ON/OFF

TSH/TEET/NORM

RH/DP/WB

AUTO-OFF

BATTERY

CHECK

ENTER

MAX/MIN/H

OUTPUT

ARH5

In-Duct 

Psychrometer

Head 

ON

AUTO OFF

1%RH/mVDC

1°F/mVDC

1°C/mVDC

LO BATT

DEW POINT

%RH

WET BULB

TEMP

°F

°C

ON

OFF

ET2W

LO BATT

SEND

RECEIVE

ON

AC

DC

Wireless

Transmitter

SYNC

Clear

Input

Output

Recall

Enter

Save

Sync

SETUP

Target

Evaporator

Logger

Light

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

HVAC  Guide

CheckMe!

Fieldpiece

HG3

Data

Service

E

Exit T

Ex

Ex

E

e

Target

arget

arget

rget

rget

get

Targe

or

ator

ato

ator

ator

ator

Ta

Evaporat

t Temp

INPUT FORM

SH Table: Standard

Refrigerant: R-22

OD Dry Bulb: 

85.4°F

Return WB: 

63.0°F

SL Pressure: 

52.4psig

SL Temp: 

45.4°F

CustomerID: 

__JONES123

Use the RCONE1 for 

hands-free in-duct 

measuremesnts.

Figure 2

  WARNING  

Do not retract the sensor probe by pulling on the cord. 

Doing so may sever the cord from the sensors.