background image

01

06

02

07

03

08

04

09

05

10

Outdoor Dry Bulb

Indoor Wet Bulb 

Battery Life

Auto Power Off Enabled

Wireless Signal Lost

Selected Refrigerant of System

Static Target Superheat Calculation

Connection Strength to Analyzer

IDWB Connection Strength

ODDB Connection Strength

Quick Start

1  Install six AA batteries into rear battery com-

partment. Batteries included in packaging.

2  Press the center blue button for 1 second to 

turn on your new manifold.

3  Connect hoses and pipe clamps  to the mani-

fold and the system.

4   See real-time pressure and temperature mea-

surements all at once!

Certifications

FCC ID:  VEARF915A

C-Tick (N22675)

CE

RoHS Compliant

Description

Your SMAN440 is a top of the line Wireless 4 

Port Manifold for HVACR professionals. See all 

your pressures and temperatures at the same 

time  on the redesigned large display with bright 

blue backlight.

SMAN440 combines high precision, absolute 

pressure sensors, a superheat/subcooling 

calculator and dual temperature measurements. 

Your SMAN440 calculates and displays target 

superheat and actual superheat to verify proper 

charge. SMAN440’s large 3/8” VAC port and true 

3/8” bore throughout the block allow for quicker 

recovery and evacuations. 

Your SMAN440 is designed to meet the 

demands of HVACR field service with a rugged 

rubber boot for durability, a strong metal 

hanger for easy storage and a form fitting, water 

resistant, padded nylon pouch.

Use additional wireless products like 

SDP2 Dual In-Duct Psychrometer to receive 

temperature measurements wirelessly for real-

time target superheat calculations.

Pressure (bar)

Pressure (pounds/in

2

)

Pressure (kilopascals or Megapascals)

Negative Pressure (inches of mercury)

Negative Pressure (cm of mercury)

Superheat

Subcooling

Target Superheat

Suction Line Temperature

Liquid Line Temperature

Vapor Saturation Temperature

Liquid Saturation Temperature

Fieldpiece

4 Port Wireless
Manifold

OPERATOR'S MANUAL

Model SMAN440              

Controls

1  Insert Type K thermocouple plugs here.

2  Temperature calibration pots.

3  Press to zero atmospheric pressure.

4  Press to calibrate to refrigerant tank.  

(See Advanced Pressure Calibration section.)

5  Press to confirm selection.

6  Press/hold to cycle through refrigerants.

7  Hold 1 second to enable wireless functionality. 

8  Press to scroll up to adjust values.

9  Press to change units.

10 Press to scroll down to adjust values.

11 Hold 1 second to power on or off. Press to toggle backlight.

12 Press to enter Target Superheat  setup mode.

13 Turn clockwise to close High side port.

14 Turn clockwise to close Low side port. 

15 Turn clockwise to close 3/8" Vacuum port.

16 Turn clockwise to close Refrigerant port. 

Functions

Superheat and Subcooling

Your SMAN440 can calculate and display both superheat and 

subcooling simultaneously. 

1   Select the appropriate refrigerant using the REFRIGERANT button.

2   Connect EPA approved refrigerant hoses to low and high side on 

SMAN440. Plug Type K thermocouple pipe clamps to SLT and LLT. 

3   Connect your SMAN440 to the system:

Superheat: 

 Hand tighten low side hose to suction line service 

port. Place the SLT pipe clamp thermocouple on the suction line  

between the evaporator and compressor, no closer than 6 inches 

to compressor. 

Subcooling:

  Hand tighten high side hose to liquid line service 

port. Attach the LLT pipe clamp thermocouple on the liquid line 

between the condenser and expansion valve (TXV), as close to the 

service port as possible.

4   After turning the system on or making any adjustments to 

the system wait 15 minutes before charging by superheat or 

subcooling to ensure the system is stabilized. 

5  To add or remove refrigerant connect a refrigerant or recovery 

cylinder to the REF port on SMAN440. Follow recommneded 

charging or recovery practices from equipment manufacturer. Use 

the low side, high side, and REF valves on SMAN440 to charge or 

recover refrigerant as needed. Let system stabilize for 15 minutes.

Note:  When superheat and/or subcooling cannot be calculated an 

"OL" or "-OL" will be displayed. Please check the following:

1  The correct refrigerant is selected on the SMAN.

2  The pipe thermocouples are plugged into SLT/LLT ports and are in 

good working condition.

3  The pipe thermocouples are attached in the appropriate location on 

the system. See step 3 above for details.

Target Superheat

 Target Superheat is useful for charging fixed orifice air conditioning 

systems.  Your SMAN440 can receive real-time indoor wet bulb (IDWB) 

and outdoor dry bulb (ODDB) temperatures wirelessly to calculate real-

time target superheat. The IDWB and ODDB values can also be entered 

both manually if measurements are taken by other instruments, or a 

combination of one wireless measurement with one manually inputted 

measurement.

Receive IDWB and ODDB temperatures wirelessly

1  Press Target SH button to enter Target SH setup mode. SMAN will 

search for last connected wireless instrument and automatically 

connect if found. Press ENTER to end search and sync to a new 

wireless instrument. IDWB will blink indicating it is ready for an 

input.

2  Hold SYNC until beep is heard to search for a Fieldpiece wireless 

instrument.

3  Set your Fieldpiece wireless instrument to connect with the 

SMAN440. Refer to your Fieldpiece wireless instrument's manual 

for more information.

4  Once SMAN440 is connected with Fieldpiece wireless instrument, 

the real-time wet bulb temperature measurement will display. 

5  Ready the Fieldpiece wireless instrument to measure indoor wet 

bulb temperature and place the probe at the return side of the 

evaporator between the filter and the coil.

6  On your SMAN440 use the ARROWS to setup ODDB. When ready, 

ODDB will be blinking.

7  Repeat steps 2 -5 for outdoor dry bulb measurements (ODDB). For 

outdoor dry bulb measurement, place the dry bulb temperature 

probe onto the side of the condenser. For accurate results, keep it 

shaded from direct sunlight.

8  Target superheat (TSH) is calculated and updated in real-time and 

located in the center column of display.

Wireless Notes  

1  For real-time target superheat calculations, both IDWB and ODDB 

measurements must be received wirelessly. 

2  A blinking HOLD will appear to the left of the TSH calculation 

when one measurement is wirelessly received and the other 

manually input indicating a static TSH calculation.

3  If the indoor wet bulb or outdoor dry bulb measurements result in 

an uncalculable TSH, 

"OL"

  or 

"-OL"  

will display. 

4  When the IDWB or ODDB is wirelessly connected with SMAN440, 

and the connection is lost, “nSG”  (No Signal) will display. 

The SMAN440 will try to reconnect with Fieldpiece wireless 

instrument for 2 minutes while the unit is powered ON. During 

these 2 minutes IDWB or ODDB can be connected to a different 

Fieldpiece wireless instrument but manual entry will be disabled.

Manually Input Temperatures

1  Press Target SH button to enter Target SH mode. Press ENTER to 

end wireless search. IDWB will blink indicating it is ready for an 

input.

2  Press UP or DOWN ARROW to toggle between IDWB or ODDB 

input. Hold ENTER to select which temperature you want to input, 

either IDWB or ODDB. The far left digit of IDWB or ODDB will begin 

blinking indicating manual input mode is ready. 

3  Press the ARROWS to change values and press ENTER to lock in 

each digit.

4  Repeat steps 2 and 3. The calculated target superheat will show in 

the center column of the display. A solid HOLD will display to the 

left of the TSH calculation indicating a static TSH calculation.

Note:  If the inputted temperature is out of the calculable range for IDWB 

or ODDB an "Err" will flash once and a double beep will sound. IDWB 

range (40°F to 125°F, 4.4°C to 51.7°C) and ODDB range (50°F to 

140°F, 10°C to 60°C). Re-input a temperature within these ranges to 

calculate target superheat.

Changing Units

Your SMAN can display pressure and temperature measurements 

in English, Metric or combination of both units.

1  Press UNITS to enter unit selection screen.

2  Use ARROW to select your desired pressure units. Press ENTER.

3  Use ARROW to select your desired temperature units. Press ENTER 

to return to pressure units.

4  Press UNITS to return to normal SMAN display.

14

16

13

15

1

1

2

2

3

4

5

8

9

11

10

12

6

7

99 Washington Street 
Melrose, MA 02176 

Phone

 781-665-

1400

Toll Free 1-800-517-8431

Visit us at www.T

estEquipmentDepot.com