SPECIFICATIONS

Display:

3½ digit liquid crystal display (LCD) with a

maximum reading of 1999.

Overrange:

"OL" mark indication.

Auto power off:

approx 60 minutes.

Operating environment:

32 to 122

°

F (0 to 50°C) at

<70% R.H.

Storage temperature:

-4 to 140

°

F (-20 to 60°C), 0

to 80% R.H. with battery removed.

Accuracy:

Specifications good in ambient condi-

tions of 73

°

F

±

9

°

F (23°C 

±

5°C), <75% relative

humidity.

Temperature Coefficient:

0.1

×

(specified accuracy)

per 

°

F/°C. (32 to 64

°

F(0 to 18°C), 82 to 122

°

F(28

to 50°C)).

Power:

Single standard 9-volt battery, NEDA 1604,

JIS 006P, IEC 6F22.

Battery life:

150 hours typical with carbon zinc,

300 hours typical with alkaline.

Accessories:

400AAC current clamp, one pair test

leads, one pair alligator clips, carrying case, 9V
battery (installed), and operating instructions.

AC Volts (50Hz - 500Hz)

Ranges:

200mV, 2000mV, 200V, 600V

Resolution:

0.1mV

Accuracy:

±

(1.2% rdg + 3 dgts) 

±

(2.0% rdg + 5 dgts) on 600V range

Input impedance:

1M

Ω

Overload protection:

600VDC or AC rms,

600VDC/AC rms 15 sec on 200mV range

Transient protection:

6kV for 10

μ

 sec

Diode Test

Test current:

1mA

Accuracy:

±

(1.5% rdg + 3 dgts)

Open circuit volts:

3.0VDC typical

Overload protection:

500VDC or AC rms

Continuity

Audible indication:

Less than 100

Ω

Visual indication: 

Green LED will be on continu-

ously.

Response time:

100ms

Overload protection:

500VDC or AC rms

Capacitance (MFD)

Range:

200

μ

F

Resolution:

0.1

μ

F

Test frequency:

42Hz

Test voltage:

<3.0V

Accuracy:

±

(3% rdg + 5 dgts)

Overload protection:

500VDC or AC rms

DC Current

Ranges:

200 

μ

A

Resolution:

0.1

μ

A

Accuracy:

±

( 1.0% rdg + 2 dgts)

Voltage burden:

1V

Overload protection: 

500VDC or AC rms

DC Volts

Ranges:

200mV, 2000mV, 200V

Resolution:

0.1mV

Accuracy:

±

(0.5% rdg + 1 dgt)

Input impedance:

1M

Ω

Overload protection:

600VDC or AC rms,

600VDC/AC rms 15 sec on 200mV range

Transient protection:

6kV for 10

μ

 sec

Resistance

Ranges:

200

Ω

Resolution:

0.1

Ω

Accuracy:

±

(1.0% rdg + 3 dgts)

Open circuit volts:

3.0VDC typical   

Overload protection:

500VDC or AC rms

THE ORIGINAL
STICK METER 
MODEL: HS26

OPERATOR’S MANUAL

HOLD

MAX

DH

PH

The Original Stick Meter

HS26

Ω

V

DC

V

AC

MFD

µA

DC

2000m

2000m

200m

200m

200

200

200

200

200

600

CAT.III 600V      200μA MAX

~

COM

V

Ω

Maintenance 

Clean the exterior with clean dry cloth. Do not use

liquid.

Battery replacement:

When the multimeter dis-

plays "      " the battery must be replaced. Disconnect
and unplug leads, turn meter off, and remove the bat-
tery cover. Replace the battery with a NEDA type 1604
9V battery.

WARNINGS

DISCONNECT AND UNPLUG TEST LEADS

before opening case.

!

!

Safety

Conforms to 

UL

61010-1, 

CE

(EN61010-1), CATIII

600V, Class II, Pollution Degree 2, Indoor Use Only. 

CATIII

:  Is for measurements performed in the build-

ing installation. 

EMC

:  Conforms to EN61326-1.

Limited Warranty

This meter is warranted against defects in materi-

al or workmanship for one year from date of pur-
chase. Fieldpiece will replace or repair the defective
unit, at its option, subject to verification of the defect.

This warranty does not apply to defects resulting

from abuse, neglect, accident, unauthorized repair,
alteration, or unreasonable use of the instrument.

Any implied warranties arising from the sale of a

Fieldpiece product, including but not limited to
implied warranties of merchantability and fitness for a
particular purpose, are limited to the above.
Fieldpiece shall not be liable for loss of use of the
instrument or other incidental or consequential dam-
ages, expenses, or economic loss, or for any claim of
such damage, expenses, or economic loss. 

State laws vary. The above limitations or exclu-

sions may not apply to you.

Obtaining Service

Call Fieldpiece Instruments for one-price-fix-all

warranty service pricing. Send check or money order
for the amount quoted. Send the meter freight pre-
paid to Fieldpiece Instruments. Send proof of date
and location of purchase for in-warranty service. The
meter will be repaired or replaced, at the option of
Fieldpiece, and returned via least cost transportation.

This instrument complies with the requirements of

the following European Community Directives:
89/336/EEC (Electromagnetic Compatibility) and
73/23/EEC (Low Voltage) as amended by 93/68/EEC
(CE Marking).

Introduction

The HS26 is smaller, simpler and more rugged

than it’s bigger brothers, and still works with all
Fieldpiece accessory heads. All Fieldpiece accesso-
ry heads slide on the top, enabling the user to test a
wide variety of parameters. All this plus the remov-
able tip test leads make safe one-handed testing a
snap.

For Your Safety

General:

Disconnect the test leads before opening

the case. Inspect the test leads for damage to the
insulation or exposed metal. Replace if suspect.
Never ground yourself when taking electrical meas-
urements. Do not touch exposed metal pipes, outlets,
fixtures, etc., which might be at ground potential.
Keep your body isolated from ground by using dry
clothing, rubber shoes, rubber mats, or any approved
insulating material. When disconnecting from a cir-
cuit, disconnect the "RED" lead first, then the com-
mon lead. Work with others. Use one hand for test-
ing. Turn off power to the circuit under test before cut-
ting, unsoldering, or breaking the circuit. Keep your
fingers behind the finger guards on the probes. Do
not measure resistance when circuit is powered. Do
not apply more than rated voltage between input and
ground.

Voltage tests:

Do not apply more than 600VDC or

600VAC to V ranges.

AC tests:

Disconnect the meter from the circuit

before turning any inductor off, including motors,
transformers, and solenoids. High voltage transients
can damage the meter beyond repair. Do not use
during electrical storms.

Symbols Used

Caution, refer to manual.

Ground

Double insulation

Alternating current

Direct current

!