GAS SPILLAGE SENSING KIT  

Model:  GSK-3, GSK-4, GSK-250M 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation of a spillage SAFETY Switch is recommended for LP and Natural gas fired systems with draft 
hoods, draft diverter, or gas barometric draft controls. This device is installed to detect flue gas spillage 
caused by a blocked flue system and/or inadequate draft. This device MUST be installed by a qualified 
installer in accordance with the manufacturer's installation instructions. Wiring MUST be in accordance 
with the National Electrical Code and applicable local codes. 

Before and after adding this safety control on existing appliances, an installation inspection in accordance 
with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis 
is recommended to determine the operating condition of the appliance. 

CAUTION:

 

Disconnect Electrical Power When Wiring Spillage Switch 

 

LOAD RATING 

MODEL 

P/N 

CONTACT 

MATERIAL 

AMPS

VOLTS 

SETPOINT °F 

RESET 

SWITCH 

TYPE 

APPLICATION 

GSK-3 

46086400 

GOLD 

24VA 

mV-24AC 

180 

MANUAL 

SPST NC 

Gas-fired mV or 24VAC 

GSK-4 

46086402 

GOLD 

24VA 

mV-24AC 

200 

MANUAL 

SPST NC 

Gas-fired mV or 24VAC, 

where slower response 

time is a requirement 

GSK-250M 

46086404 

SILVER 

24VA 

mV-24AC 

250 

MANUAL 

SPST NC 

Steam Boilers 