background image

www.fi eldcontrols.com

Please retain these instructions after installation.

This device MUST be installed by a qualifi ed agency in accordance with the manufacturer's installation instructions. The defi nition 

This device MUST be installed by a qualifi ed agency in accordance with the manufacturer's installation instructions. The defi nition 
of a qualifi ed agency is: any individual, fi rm, corporation or company which either in person or through a representative is engaged 

of a qualifi ed agency is: any individual, fi rm, corporation or company which either in person or through a representative is engaged 
in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the 

in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the 
precautions required, and has complied with all the requirements of the authority having jurisdiction.

precautions required, and has complied with all the requirements of the authority having jurisdiction.

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

Installation Date:

Installed By:

Phone:

UV-AIRE AIR PURIFYING SYSTEM

Model: CUV AND DUV SERIES

ITEMS INCLUDED IN SYSTEM:

• 

Magnetic Mount Power Enclosure

• 

Lamp Support Rod(s)

• 

Ultraviolet Lamp(s)

• 

Access Panel Warning Label

• 

Instruction Manual

• 

Tie Wraps

• 

Lamp Install Label

• 

Lamp Cleaning Kit

P/N 780108800 Rev A 10/22

The UV‐Aire unit is designed to emit High Output UVC Wavelength light rays which inactivate and sterilize 
airborne microorganisms as they pass through a HVAC system or ductwork. The UV-Aire Purifying System  
models have been designed for use as coil irradiation and/or for air disinfection.

This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or 
condition, nor for use in the mitigation, treatment or prevention of any disease or condition.

The aspects associated with the use of this product and its ability to aid in disinfection of environmental air 
have not been investigated by UL.

AIR DUCT MOUNTED ACCESSORY

WITH RESPECT TO ELECTRICAL SHOCK, 

FIRE AND CASUALTY HAZARDS ONLY

E524561

Содержание CUV Series

Страница 1: ...ority having jurisdiction READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Installation Date Installed By Phone UV AIRE AIR PURIFYING SYSTEM Model CUV AND DUV SERIES ITEMS INCLUDED IN SYSTEM Magnetic Mount Power Enclosure Lamp Support Rod s Ultraviolet Lamp s Access Pane...

Страница 2: ...page 2 of 20 THIS PAGE LEFT INTENTIONALLY BLANK P N 780108800 Rev A 10 22 ...

Страница 3: ...her affected skin area with mild detergent Remove affected clothing immediately If skin surface is pierced seek medical attention immediately If UV lamp breaks clean and dispose of with the same care as a fluorescent lamp UV lamps must be disposed of in accordance with local state and federal environmental disposal laws CAUTION Equipment damage hazard Ultraviolet light can cause color shift or surf...

Страница 4: ...ute autre zone de la peau affectée avec un détergent doux Retirez immédiatement les vêtements touchés Si la surface de la peau est percée consultez immédiatement un médecin Si la lampe UV se casse nettoyez et jetez la avec le même soin qu une lampe fluorescente Les lampes UV doivent être éliminées conformément aux lois locales étatiques et fédérales sur l élimination de l environnement LAPRUDENCE R...

Страница 5: ...e alternative screw mounting method if not directly mounted to a metal surface metal surface and or has excessive vibration or mounting surface is not horizontal Route power cable and uv lamp cable s in a manner to shield or limit exposure to ultraviolet rays If cables are in direct exposure to lamp ultraviolet rays then cover wrap cables with foil tape Use the extra tie wraps to secure the cables...

Страница 6: ...noncoated and coated The coated lamps have a fluoropolymer film coating to assist glass and mercury containment should the lamp get broken This fluoropoly mer film coating reduces the overall lamp UV intensity output by a few percentage Coated and noncoated UV lamps are interchangeable with in the UV series product offering The coated UV lamps are more expensive than the noncoated UV lamps Coated ...

Страница 7: ...to match the UV lamp pins Align the lamp pins with the connector and push together If connection is not made easily rotate the connector 90 and then push together The proper lamp connection should match Figure 4B CERAMIC PLASTIC END SECTION OF UV LAMP Figure 4A UV Lamp Cable Connector and Lamp Pins Figure 4B Proper Cable and Lamp Connection INVERTED U SHAPED BRACKET LA PRUDENCE N insérez PAS fixez ...

Страница 8: ...nel of the appli ance This should be the same access panel where the Electrical Interlock Switch assembly is installed to deactivate power down UV product when panel is removed Fill in installation date or in service date for the UV Lamps on the UV Lamp Installation Label using permanent marker and affix label some place near the UV Lamps access panel as a reminder to replace the lamps every two 2...

Страница 9: ...page 9 of 20 Diagram 1 Electrical Wiring Schematic for xUV 11xxxx Model Product P N 580012801 Rev A NOTE USE COPPER SUPPLY LINES FOR ALL ELECTRICAL WIRING P N 780108800 Rev A 10 22 ...

Страница 10: ...page 10 of 20 Diagram 2 Electrical Wiring Schematic for xUV 15xxxx Model Product P N 580012802 Rev A NOTE USE COPPER SUPPLY LINES FOR ALL ELECTRICAL WIRING P N 780108800 Rev A 10 22 ...

Страница 11: ...ded to be all exclusive and limited to but to assist the installer with where and how to install this product There are infinite other product installation orientations which can be acceptable by following the basic information and guidelines provided within this manual Figure 7 Generic Example of Rooftop HVAC Supply Air Side Installation Figure 8 Generic Example of Rooftop HVAC Return Air Side In...

Страница 12: ...page 12 of 20 Figure 9 Generic Example of Rooftop HVAC Return Air Side Installation Figure 10 Generic HVAC Ductwork Installation Horizontal Rod Support P N 780108800 Rev A 10 22 ...

Страница 13: ...ion as shown in Figure 12 the cable connection point to the lamps should be at the lowest point of the lamp ie do not orient lamps to be plugged in from the top LA PRUDENCE Lorsque les lampes UV sont installées dans une orientation verticale comme le montre la figure 12 le point de connexion du câble aux lampes doit être au point le plus bas de la lampe c est à dire ne pas orienter les lampes à bra...

Страница 14: ...261 1301 Single Magnet Lamp Support Bracket Qty 2 60261 1305 Conduit Lamp Support Bracket Qty 2 60261 1306 OPTIONAL LAMP AND EMT CONDUIT MOUNTING ACCESSORIES P N 780108800 Rev A 10 22 Figure 14 Dual Lamp Support Rod Assembly for Dual Lamp Models Optional Figure 13 Single Lamp Support Rod Assembly for Single Dual Lamp Models Standard EMT Conduit Magnetic Mounting Bracket Inverted U Shaped Lamp Brac...

Страница 15: ...orm 45 and 90 bracket configurations See Figure 15 Standard Configuration for EMT Tri Foot Magnet Conduit Bracket Assembly is what is supplied from factory for all rod assemblies with UVC lamp lengths of 38 thru 58 in length Bracket hardware can be reconfigured to form 45 and 90 bracket configurations The EMT Tri Foot Magnet Conduit Bracket Assembly is shipped with bottom tri foot plate with magnets i...

Страница 16: ...th a formed mounting bracket lamp cable cover plate two panel pass thru cable con nectors hardware and mount ing instruction sheet Figure 20 EMT Tri Foot Magnet Partial Assembly Exploded View OPTIONAL LAMP SHIELDS Optional Lamp Shields can be added to lamp support rod assemblies to shield some areas from UVC rays and direct the UV intensity towards a specific area as shown in Figure 22 The lamp shi...

Страница 17: ...fastener hardware is tight after installation 8 Apply power to UV system a Close Electrical Interlock Switch and verify UV lamp s lite up b Fill in Date on UV Lamp Installation Label and affix lamp label to installation 9 Install Electrical Interlock panel service panel MAINTENANCE AND TROUBLESHOOTING WARNING Disconnect power to the appliance before commencing with inspection cleaning and or part ...

Страница 18: ...c Power Enclosure Sliding Downward Metal surface dirty or too much vibration Install screws into magnetic lamp rod or power enclosure endplate flanges to secure in place TROUBLESHOOTING GUIDE Replacement Schedule UV Lamps should be replaced every two years or 18 000 hours of operation Ballast should be replaced every five years or 50 000 hours of operation Inspection Procedure Remove Access Panel ...

Страница 19: ...ble DUV xxxxxx 60261 1 101 CUV LC 12 Ft Nominal Lamp Cable CUV xxxxxx 60261 1 103 CUV PC 9 Ft Nominal Power Cable All Models 60261 1 104 CUV DC 12 Ft Nominal CUV RIMM Display Cable xUC 15xxxxxx 60261 1 105 CUV DISP Display Only Replacement xUV 15xxxxxx 620177500 CUV OMK Outdoor Mounting Kit All Models 602610918 CUV SHIELD18 UV Shield For 17 5 CUV Lamp xUV 1 1 18xx 602610923 CUV SHIELD23 UV Shield ...

Страница 20: ... com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information about this or any Field Controls product visit For warranty information about this or any Field Controls product visit www fieldcontrols com www fieldcontrols com Field Controls Customer Service Field Controls Customer Service 252 522 3031 252 522 3031 ...

Отзывы: