Hydro Logger H1
User manual
68
electronics for ecology
FIEDLER
6.9.
Warning and control SMS
Automatic sending of a preset warning or control SMS can be triggered not only
by exceeding the preset limit value on the measuring channel, but also by a
change in the state of the binary channel, an error in the measuring signal, acti-
vation or deactivation of an alarm on the channel, etc.
The Hydro Logger H1 continuously evaluates the current measured values on
both analogue and binary channels. If the value exceeds the set limit or if a binary
input is switched on or off, it sends a pre-prepared SMS to selected mobile pho-
nes.
For integral variables (instantaneous or cumulative flow, rainfall, number of pul-
ses, ...), the activation of the SMS warning can also be triggered by exceeding a
pre-set limit value for a certain time.
Warning messages are the basic and most frequently used type of SMS in the
communicator. The features of warning SMS can be summarized in the
following points:
▪
The user can set the text of up to fourteen different warning messages.
▪
At the beginning of each alert SMS it is possible to automatically insert
the name of the device sending the message and the current time in the
device at the time of sending the SMS. Only then is the actual text of the
message followed.
Note: in special cases, such as sending a message to a special operator
number that forwards incoming messages to e-mail, it is necessary to di-
sable the automatic insertion of the name tag and time.
▪
For each message, you can select the recipient from a list of authorised
persons. You can also create a group of persons to whom the SMS will
be sent in turn.
▪
The sending of the message can be conditioned by the time period for
which the activation condition of the message must be fulfilled
S t a r t i n g
c o n d i t i o n s
A c t i v a t i o n b y s u m
P r o p e r t i e s o f
w a r n i n g m e s s a g e s
When you select a group as
recipient, the same SMS is
sent to each member of the
group in turn
There are 14 SMS alerts
Phonebook for 10 recipi-
ents that can be grouped
together.
SMS will be sent
only after the conti-
nuous duration of
the trigger condition
Prevents frequent
sending of SMS
when the variable
moves around the li-
mits.
Text without ac-
cents. Special cha-
racters allow auto-
matic insertion of
the instantaneous
value of the mea-
surand.
You can temporarily
or permanently disa-
ble an SMS that you
have already set up.
The set parameters
will be preserved.
Trigger condition, after
which the warning SMS is
activated
Limit value, after which the
warning SMS will be activa-
ted
Содержание H1
Страница 1: ...Small telemetry station for water applications H1 H2 Hydro Logger user manual version 1 10 ...
Страница 2: ...Hydro Logger H1 User manual 2 electronics for ecology FIEDLER ...
Страница 80: ...Hydro Logger H1 User manual 80 electronics for ecology FIEDLER Notes ...
Страница 81: ...Hydro Logger H1 User manual FIEDLER electronics for ecology 81 ...