Using the WPM Gateway
7.4.3.2
Current parameters of a sensor
Current parameters of a sensor
In this view, the currently set parameters of a sensor are displayed.
Open view:
Main menu => Data holder =>
=> Sensor =>
=> Configuration
Fig. 7-12 Current parameters of a sensor
Fields
Name
Meaning
Sensor
name
Self-assigned name for the sensor (maximum 15 characters).
Lock
If this option is enabled, the configuration of the sensor is only changed after
confirmation via a confirmation prompt.
Pressure
warning
Limit value (in bar) that triggers a warning if it is undershot.
Maximum
pressure
warning
Limit value (in bar) that triggers a warning when exceeded. Nothing is speci-
fied as the default value, so, in this case, there is no warning if the maximum
pressure is exceeded.
Pressure
alarm
Limit value (in bar) that triggers an alarm if it is undershot.
Temperature
warning
Limit value (in °C) that triggers a warning if exceeded.
Temperature
alarm
Fixed limit value (in °C) that triggers an alarm if exceeded. (preset to 70°C).
Measurement
interval
Time interval at which the sensor should take measurements.
Transmission
interval
Time interval (0.1 to 10 seconds) at which the Bluetooth Low Energy Advertis-
ing packets are to be sent. A high time interval has a positive effect on the en-
ergy consumption of the data holder.
Channel
37/38/39
Bluetooth Low Energy Advertising channels to be used for Advertising.
Save configuration
Save