FIAMM SoNick I&O - 48TL160H rev.0
– July 2013
pag.9
1
Negative battery terminal
M8,female
2
Power switch
-
3
USB port
USB type B
4
Not used
-
5
Positive battery terminal
M8, female
6
Com port output
(RS485/CanBus)
RJ-45
7
Com port input
(RS485/CanBus)
RJ-45
8
Alarm configuration jumper
-
Table D
3.4 Power Cable Connection
Do not connect in series two or more batteries.
Parallel connection is allowed.
Each 48TL160H battery is a 48 Vdc battery and is to be considered as a 48 Vdc battery
system.
If there is a
switch in the battery line, please turn it off before connecting the power
cables to the battery
. Otherwise please note that sparks may occur. In any case the
battery and the BMS are not damaged.
3.4.1 Individual connection
1) Remove the terminal insulation covers by pulling them as in the figure n°6 below
Figure 6
2
) Ensure that the battery switch is in the OFF position (Fig.7)