FIAMM SoNick I&O - 48TL160H rev.0
– July 2013
pag.10
Figure 7
3) Connect the negative DC power supply terminal to the negative terminal of the battery (1,
fig.5).
4) Connect the positive DC power supply terminal to the positive terminal of the battery (5,
fig.5).
5) Power terminal bolts should be torqued to 7-8 Nm (5-6 Ft/Lbs,60-70 In/Lbs). Install the
terminal insulator cover on the terminal bolts to protect the battery terminals from accidental
contact/short circuit.
6) If a Ground connection is necessary, a bolt on the side of the battery can be used, as
indicated in the picture 8 below.
7) If no data connection is being used, secure all the protective dust caps provided with the
battery on each data port.
Figure 8
3.4.2 Parallel Connection
48TL160H batteries can be connected in parallel to the same rectifier. There is no limit in
the number of the batteries that can be paralleled
1)
Before connecting any cables, match proper polarity (only connect positive to positive
and negative to negative).
2)
Connect the positive terminal of each battery together or to the same DC bus bar
3)
Connect the negative terminal of each battery together or to the same DC bus bar