FlameSpec

 

UV-IR 

User Manual

 

F110V0020.05 

 

 

 

 

 

 

FlameSpec 

UV-IR 

FlameSpec 

UV-IR-F

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание FlameSpec UV-IR

Страница 1: ...FlameSpec UV IR User Manual F110V0020 05 FlameSpec UV IR FlameSpec UV IR F www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...purposes such as selling copies of this publication or for providing paid for support services The Fire Gas Detection Technologies logo is a trademark of Fire Gas Detection Technologies Inc registered...

Страница 3: ...5 Installing the Tilt Mount 7 2 6 Installing the detector 8 3 Configuration options 10 3 1 Sensitivity 10 3 2 Ultra Fast Detection 11 3 3 Alarm Delay 11 3 4 Alarm Latch 11 3 5 Window Heater 11 3 6 Mo...

Страница 4: ...ntal Specifications 20 6 6 Label Figures 21 6 7 Approvals 22 6 8 Electromagnetic Compatibility 22 7 Warranty 23 Appendix A Response Characteristics FLS UV IR 24 A 1 Response to different fire scenario...

Страница 5: ...t Side View 9 Figure 4 Source 4 Wire Scheme 13 Figure 5 Sink 4 Wire Scheme 13 Figure 6 Source 3 Wire Scheme 14 Figure 7 Sink 3 Wire Scheme 14 Figure 8 RS 485 Networking 15 List of Tables Table 1 Detec...

Страница 6: ...R Hydrogen and hydrocarbons flame detection Spectrum response of IR radiation in the 3 0 4 0 micron range 2 FLS UV IR F Hydrocarbon flame detection Spectrum response of IR radiation in the 4 0 5 0 mic...

Страница 7: ...rforms self tests of its optics electronics and software These include a periodic BIT Built In Test in which the sensors and window cleanliness are tested Any detected fault is indicated as shown in T...

Страница 8: ...tected area Whenever possible the detector face should be tilted aimed down at an angle to prevent the accumulation of dust and dirt Do not start an installation until the detector task definition sys...

Страница 9: ...lity of a false alarm cannot be tolerated Gas welding requires a system inhibit since the gas torch is an actual fire Arc welding rods can contain organic binder materials in the flux that burn during...

Страница 10: ...wires for the site wiring The selection of wire gauge should be based on the number of detectors used on the same line and the distance from the control unit in compliance with specifications Use wir...

Страница 11: ...rial s data sheet that it is resistant to specific chemicals 2 4 1 Specific conditions for use The equipment is not intended to be repaired by the user Repair of this equipment shall be carried out by...

Страница 12: ...e detector from above Other designated adapters may be used to connect the detector to some other vendors tilt mounts useful when replacing an existing detector To install the tilt mount a Place the t...

Страница 13: ...ock washers Items 3 and 4 d Release the locking screws Items 5 and 6 in such a way that enables you to rotate the detector e Point the detector towards the detection area and make certain that the vie...

Страница 14: ...ctor on Tilt Mount Side View ITEM NO ITEM NAME 1 TILT MOUNT ASSEMBLY 2 HOLDING PLATE 3 4 MOUNTING HEX SCREWS M8 AND LOCK WASHERS 5 HEX SOCKET LOCKING SCREW M8 6 HEX SOCKET LOCKING SCREW M12 3 4 1 6 2...

Страница 15: ...indow Heater Disabled Enabled Enabled Modbus address 1 247 1 Manual BIT Alarm Output Test Disabled Enabled Disabled Note Medium sensitivity setting allows detection of a 1x1ft2 0 1m2 N heptane pan fir...

Страница 16: ...o normal mode the detector must be powered down and restarted 3 5 Window Heater The detector is equipped with a heater to prevent condensation and icing on the window If enabled the heater is operated...

Страница 17: ...T contact relay that is energized closed when the detector is in normal operation and opens in case of fault 6 Fault Relay COM 7 Alarm Relay NO A normally open SPST contact relay that is open in norma...

Страница 18: ...wire the detector to act as a current source isolated transmitter 4 wire connection FIGURE 4 SOURCE 4 WIRE SCHEME The following drawing shows how to wire the detector to act as a current sink isolated...

Страница 19: ...tter 3 wire connection FIGURE 6 SOURCE 3 WIRE SCHEME The following drawing shows how to wire the detector to act as a current sink non isolated transmitter 3 wire connection FIGURE 7 SINK 3 WIRE SCHEM...

Страница 20: ...ing repeaters the number of detectors can be much larger 32 detectors for each repeater up to 247 on the same 4 wires Using the RS 485 network it is possible to read each detector s status fault alarm...

Страница 21: ...ibed in section 3 To restart the detector turn off and then turn on the power 5 1 Output Signals The detector has the following output signals Current output 0 20mA Relays Fault and Alarm RS 485 Tri c...

Страница 22: ...WARNING Make sure to disable all fire extinguishing actions or alarms connected to the detector when the manual BIT is initiated and the Manual BIT Alarm Output Test is enabled as the manual BIT will...

Страница 23: ...ity Check wiring in the detector Yellow LED constantly on Fault Relay is open Current output at 0mA Power problems Check the voltage between the 24VDC and 24VDC terminals to verify that it is in the a...

Страница 24: ...l Time Delay 0 30 seconds adjustable Built in test Automatic and Manual 6 2 Electrical Specifications Operating Voltage 24 VDC nominal 18 32 VDC Current Consumption o Standby 120mA o Maximum 180mA all...

Страница 25: ...l 4 mA 10 IR Detected 8mA 10 UV Detected 12mA 10 Alarm 20 mA 5 Tri colour LED indication Modbus RTU compatible protocol on RS 485 6 4 Mechanical Specifications Size 5 51 x 3 54 3 54 140 90 90mm Weight...

Страница 26: ...FlameSpec UV IR User Manual F110V0020 05 6 6 Label Figures 6 6 1 Ex db 6 6 2 Ex db eb www acornfiresecurity com www acornfiresecurity com...

Страница 27: ...B C D T4 Class I Zone 1 AEx Ex db IIC T4 Gb T4 50 C Ta 85 C T5 50 C Ta 75 C Performance o ANSI FM 3260 o EN 54 10 Functional safety pending SIL 2 per IEC 61508 DNV GL Designed to meet standard DNVGL C...

Страница 28: ...improper installation lack of maintenance or Act of God which are above and beyond its control FIRE GAS DETECTION TECHNOLOGIES INC will upon receipt of any defective product transportation prepaid re...

Страница 29: ...ce Feet m Average Response Time Seconds N Heptane 1 x 1 ft 98 30 2 0 Gasoline 2 x 2 ft 197 60 3 3 Gasoline 1 x 1 ft 98 30 1 8 Methane 32 in Plume 59 18 1 4 LPG 32 in Plume 75 23 1 2 Diesel 1 x 1 ft 75...

Страница 30: ...1 2 JP5 1 x 1 ft 36 11 1 2 Kerosene 1 x 1 ft 36 11 0 9 Methanol 1 x 1 ft 30 9 1 3 Ethanol 1 x 1 ft 31 9 5 2 9 Isopropanol 1 x 1 ft 36 11 0 8 Polypropylene 1 x 1 ft 23 7 0 9 Paper 1 x 1 ft 23 7 1 0 H2...

Страница 31: ...either modulated or non modulated False Stimuli only at Extreme Sensitivity False Alarm Source Maximum Distance in ft m Sunlight Direct Reflected Incandescent frosted glass light 300W 2 0 5 Fluorescen...

Страница 32: ...5 3 Gasoline 1 x 1 ft 98 30 3 4 Methane 32 in Plume 59 18 1 6 LPG 32 in Plume 75 23 1 2 Diesel 1 x 1 ft 75 23 4 3 JP5 1 x 1 ft 75 23 7 0 Kerosene 1 x 1 ft 75 23 2 9 Methanol 1 x 1 ft 59 18 3 6 Ethano...

Страница 33: ...to Extreme sensitivity For each radiation source a distance is listed This is the minimum tested distance from which the detectors did not alarm when exposed to the radiation source either modulated...

Страница 34: ...FlameSpec UV IR User Manual F110V0020 05 www acornfiresecurity com www acornfiresecurity com...