18
Festo — VPPI-...-S1BT — 2021-11
Commissioning
8.2.7
‘Set point’ parameter group
Parameter
Contents
Description
‘Input type’
‘Analog’/‘Digital’
–
‘Analog’: the setpoint pressure is specified as an
analogue voltage/current value via the set value
input.
–
‘Digital’: a digital 24 V signal is entered via the
setpoint input.
‘Maximum analog
setpoint’
e.g. 5 V
Upper limit of the analogue setpoint value range.
The ‘Minimum analog setpoint’
>
‘Maximum analog
setpoint’ setting is not recommended.
‘Minimum analog
setpoint’
e.g. 0 V
Lower limit of the analogue setpoint value range.
The ‘Minimum analog setpoint’
>
‘Maximum analog
setpoint’ setting is not recommended.
‘Pressure value
001’
e.g. 1.00 bar
Setpoint value, if value of the digital inputs = 001
‘Pressure value
010’
e.g. 2.00 bar
Setpoint value, if value of the digital inputs = 010
‘Pressure value
011’
e.g. 4.00 bar
Setpoint value, if value of the digital inputs = 011
‘Pressure value
100’
e.g. 5.00 bar
Setpoint value, if value of the digital inputs = 100
‘Pressure value
101’
e.g. 7.00 bar
Setpoint value, if value of the digital inputs = 101
‘Pressure value
110’
e.g. 8.00 bar
Setpoint value, if value of the digital inputs = 110
‘Pressure value
111’
e.g. 10.00 bar
Setpoint value, if value of the digital inputs = 111
Tab. 10: Input values
If the ‘Digital’ input is selected, one of 8 setpoint values is specified via three 24 V inputs. For this, the
three inputs are interpreted as a binary number with 3 bits.
The assignment is as follows:
• Setpoint value (+): DI0 or least significant bit
• Setpoint value (-): DI1
• Actual value output: DI2 or most significant bit
The value 000 means 0 bar, the remaining 7 values can be set in ‘Set point’