Festo SOPA Series Скачать руководство пользователя страница 2

5.1.2.1

Symbols on the Display

Symbol

Description

Display of binary signals set/not set (in example A, B: set - C: not set)

1)

Threshold Value Comparator

Window Comparator

[SP]

Switching point

[SP][min]

Lower switching point

[SP][max]

Upper switching point

[HY]

Hysteresis

[NO]

Switching characteristic of normally open contact

[NC]

Switching characteristic of normally closed contact

[min]/[max]

Minimum/maximum input value (in A/B/C)

[Delay]

Switch-off delay for the numerical display

[Analogue]

Settings for analogue output

[TeachIn]

Teach mode active

[Option]

Options for spurious pulse suppression (Off, 1, 2)

[Lock]

Security code active (block to prevent unauthorised parameterisation)

[Spec]

Special menu (SPEC) active

[di.]

Activation/deactivation of the numerical display
Switching off the display backlight

[PnP]/[nPn]

Switching the switching output

[P2-]

Allocation of the switching output for Pin 2 with the binary signal OutB or OutC

[P4-]

Allocation of the switching output Pin 4 with the binary signal OutA or OutC

[rP.]

Replicate settings to another device

[F.]

Set the time constant of the low-pass filter for analogue output

[0..10]/[1.. 5]

Switching of the voltage output

[H.]

Scaling of the analogue output end value

[L.]

Scaling of the analogue output start value

[----]

Numerical display is switched off

[IOL]

Flashes 3x when Edit mode is blocked by IO-Link

[SUP.P]

Error message: Supply pressure is outside the set limits (SP

min

/SP

max

)

[CLER]

Device has been reset to factory settings

Graphical display of the current distance-correlated value for InA and InB in relation
to the set switching point 

The bar graph for InA is always active.

The bar graph for InB is only active if the binary signal OutB is assigned to the
switching output at Pin 2.

1) "A" flashes when IO-Link communication is active

Tab. 3 Symbols on the Display

5.1.2.2

Bar Graph on the Display

Display

Description

Segment at the bottom left and
[A] flash

INFO mode active.

7-segment display shows the input value
InA.

Segment at the bottom left and
[A] illuminate, [min] or [max]
flash.

SHOW mode active.

7-segment display shows the minimum or
maximum value InA.

Segment at the bottom right
and [B] flash.

INFO mode active.

7-segment display shows the input value
InB.

Segment at the bottom right
and [B] illuminate, [min] or
[max] flash.

SHOW mode active.

7-segment display shows the minimum or
maximum value InB.

Segments at the bottom right
and left and [C] flash.

INFO mode active.

7-segment display shows the input value
InC.

Segments at the bottom left
and right and [C] illuminate,
[min] or [max] flash.

SHOW mode active.

7-segment display shows the minimum or
maximum value InC.

Marked segments illuminate
and [Option] flashes.

EDIT mode active.

Special menu opens.

7-segment display shows the set option.

Marked segments illuminate
and [Lock] flashes.

EDIT mode active.

Special menu opens.

7-segment display shows the security code.

Tab. 4 Special Bar Graphs on the Display

5.2

Function

5.2.1

Functional Principle

The system consists of two sub-components. The control module provides a com-
pressed air preparation that is adapted to the supply pressure of the sensor mod-
ule, as well as the functionality for switching measuring and exhaust air. Up to
4 sensor modules contain the sensory functions. The sensor modules can be
operated both individually and in combination with the control module.

1 3/2-way valve (instrument air)

2 Pressure regulator

3 3/2-way valve (exhaust air)

4 Supply pressure

5 Sensor modules (pneumatically

linked)

6 Object (example)

7 Air gap

8 Measuring nozzles (1 per sensor

module)

9 Vent screw

10 Supply port for operating pressure

Fig. 3 Configuration with a control module and two sensor modules

The compressed air flows from the sensor modules to the measuring nozzles. If
the object is very close to a measuring nozzle, the air gap is very small and only a
small amount of air flows through. As the object gets further away, the air gap
becomes larger and more air flows through. The change in flow rate is detected by
the sensor modules, converted into a distance-correlated value and displayed
(speed measuring method with ejector).

5.2.2

Operating Statuses

Operating status

Function

RUN Mode

Basic status after the operating voltage is applied

Numerical and graphical display of distance-correlated values (bar
graph)

Display of measured values for supply pressure (in bar)

Display of the signal statuses of the binary signals OutA, OutB, OutC

INFO mode

Display of input variables in the display

Switch the display by pressing the A pushbutton and/or the B push-
button

SHOW mode

Display of current settings for the binary signals,

Display and reset of the min/max values for the distance-correlated
value and supply pressure

EDIT Mode

Setting or alteration of the parameters for the air gap sensor (switch-
ing outputs, display)

TEACH mode

Teaching-in of the switching points for the distance-correlated values
(transfer of the current value as the trigger level).

Tab. 5 Operating Statuses

5.2.3

Switching Outputs

5.2.3.1

Switching Signals

1 Sensing variable

2 Input signal

3 Binary signal

4 Switching signal at sensor module

plug

Fig. 4 Binary signals and switching signals SOPA-...-2P/2N-...

Содержание SOPA Series

Страница 1: ...be used with a Class 2 power source or Class 2 trans former in accordance with UL1310 or UL1585 As an alternative a LV C Limited Voltage Current power source with one of the following properties can b...

Страница 2: ...ft and right and C illuminate min or max flash SHOW mode active 7 segment display shows the minimum or maximum value InC Marked segments illuminate and Option flashes EDIT mode active Special menu ope...

Страница 3: ...NC normally closed In Supply pressure Switching function 2 switching points SPmin SPmax IO Link SP1 SPmin SP2 SPmax No TEACH mode Tab 7 Window Comparator Hysteresis Hysteresis serves to suppress switc...

Страница 4: ...supply use only PELV circuits in accordance with IEC 60204 1 EN 60204 1 Protective Extra Low Voltage PELV Observe the general requirements of IEC 60204 1 EN60204 1 for PELV cir cuits Only use voltage...

Страница 5: ...the desired switching distance between the object and the measur ing nozzle 2 Press A pushbutton and keep it pressed 3 Additionally press the Edit button OutA and TeachIn flash The value is adopted a...

Страница 6: ...s 11 Malfunctions 11 1 Fault Clearance Fault description Cause Remedy Supply voltage not applied or permitted operating voltage not present Switch on the supply voltage observe the voltage range Elect...

Страница 7: ...able Switching function OutA Threshold value comparator with variable hysteresis OutB Threshold value comparator with variable hysteresis OutC Window Comparator Switching element function N C contact...

Страница 8: ...35 mm to DIN EN 60068 part 2 6 Tab 31 Immissions Emissions IO Link Protocol version Device V1 1 Device V1 1 Smart sensor profile Function classes Switching signal channel SSC Process data variable PDV...

Отзывы: