Festo SDE5 series Скачать руководство пользователя страница 1

Translation of the original instructions

1

Safety

1.1

General safety instructions

Only use the product in original status without unauthorised modifications.

Only use the product if it is in perfect technical condition.

Observe labelling on the product.

Condensation, oil mist, foreign matter and other contaminants in the com­
pressed air can damage the product. Only use media in accordance with the
specifications 

è

 Technical data. 

This product can generate high frequency interference, which may make it
necessary to implement interference suppression measures in residential
areas.

1.2

Intended use

The SDE5 is intended for pressure monitoring of gaseous media in piping systems
or terminal equipment in industry.

1.3

Training of qualified personnel

Installation, commissioning, maintenance and disassembly should only be
conducted by qualified personnel.

1.4

Area of application and approval

The information in this section, in combination with the UL marking on the
product, must be observed in order to ensure compliance with the certification
conditions of Underwriters Laboratories Inc. (UL) for USA and Canada. Observe
the following information in English by UL:
In determining the acceptability of the combination, the following details should
be examined:

The mounting suitability shall be determined in the end­use.

These devices shall be mounted in an enclosure having adequate strength
and thickness.

Devices should be used within its recognized ratings as specified under sec­
tion RATINGS.

Devices have to be supplied from:

A Class 2 power source or Class 2 transformer in accordance with UL1310
or UL1585, or 

An isolating device such that the maximum open circuit voltage potential
available to the circuit is not more than 30 Vdc and the current is limited
to a value not exceeding 8 amperes measured after 1 minute of opera­
tion, or 

A suitable isolating source in conjunction with a fuse in accordance with
UL248. The fuse shall be rated max. 3.3 A and be installed in the 30 Vdc
power supply to the device in order to limit the available current. 

Note that, when more than one power supply or isolating device is used, connec­
tion in parallel is not permitted.

The devices have not been investigated for field­wiring.

The suitability should be determined in the end­use application.

UL approval information

Product category code

NRNT2 (USA) and NRNT8 (Canada)

File number

E253738

Considered standards

UL 508, 17th edition, C22.2 No.14­05

UL mark

Tab. 1 UL approval information

2

Further information

Accessories 

è

 www.festo.com/catalogue.

Spare parts 

è

 www.festo.com/spareparts.

3

Service

Contact your regional Festo contact person if you have technical questions

è

www.festo.com.

4

Product overview

4.1

Configuration

4.1.1

Product design

1 Electrical connection

2 LED indicator (continuous trans­

mission of the LED indicator
through fibre­optic cable)

3 Connection 2 for compressed air or

vacuum

4 Connection 1 for compressed air or

vacuum

5 Edit button (not on SDE5­...X)

Fig. 1 Product design SDE5

MS series service unit component with pressure sensor SDE5

The pressure sensor SDE5 on the series MS service unit component is already per­
manently attached and pneumatically connected in the delivery status.

1 Edit button

2 LED indicator (continuous trans­

mission of the LED indicator
through fibre­optic cable)

3 Electrical connection

Fig. 2 SDE5 installed on the MS series service unit component

MS series service unit component

Attached pressure sensor

MS4/6­...­AD7

SDE5­D10­O­...­P­M8

MS4/6­...­AD8

SDE5­D10­C­...­P­M8

MS4/6­...­AD9

SDE5­D10­O3­…­P­M8

MS4/6­...­AD10

SDE5­D10­C3­...­P­M8

Tab. 2 Assignment of service unit component MS and attached pressure sensor

4.1.2

LED display

LED

Meaning

LED illuminated
(yellow)

SDE5­...­P/­N­... (switching output): pressure p > switching pressure

LED off

SDE5­...­P/­N­... (switching output): pressure p < switching pressure

LED flashes
quickly
(yellow)

Teach procedure

LED flashes slowly
(yellow)

Only SDE5­...­FP: display and setting of the switching function

LED illuminated
(green)

Only SDE5­...­V (analogue output): ready status (RUN mode)

Tab. 3 Meaning of the LED indicator

4.2

Function

4.2.1

Functional principle

The SDE5 converts pneumatic pressure values into a voltage proportional to the
pressure. Depending on the design of the pressure sensor, the voltage signal is
converted into a digital switching signal (SDE5­...­P­.../SDE5­...­N­..) or amplified
for an analogue output (SDE5­...­NF­...­V).

8110091

SDE5

Pressure sensor

8110091
2019­06f
[8110093]

Instructions | Operating

Festo SE

 & Co. KG 

Ruiter Straße 82 
73734 Esslingen 
Germany
+49 711 347­0

www.festo.com 