Festo — CPX-AP-A-PN-M12 — 2022-07
Diagnostics and fault clearance
15
ID hex (dec)
Message
Description
08 | 01 | 01AD
(134283693)
System state change
to OPERATION failed
Remedy
–
Restart system
–
Update firmware to latest version
–
Contact Festo service
Diag-
nostic
status
Warning
08 | 01 | 01AE
(134283694)
AP device invalid
detected
For the AP device the device state "device invalid" was
detected.
Remedy
–
Check AP device
–
Restart system
Diag-
nostic
status
Error
08 | 01 | 01B1
(134283697)
AP Startup delayed
Unexpected error during startup. Automatic retry of
startup triggered.
Remedy
–
Check communication cable (AP)
–
Check AP devices
–
Check for firmware versions
Diag-
nostic
status
Warning
08 | 01 | 01C4
(134283716)
AP Module(s)
detected
One or more new AP module(s) were detected in the
system.
Remedy
–
None
Diag-
nostic
status
Information
08 | 01 | 01FF
(134283775)
Device not ready
A device is delaying the startup excessively long.
Remedy
–
Contact Festo Support
Diag-
nostic
status
Error
08 | 01 | 0215
(134283797)
Device forced to com-
munication loopback
The device was forced by the master to set the loopback
on the communication port, due to commnuication errors.
Communication to subsequent modules is thereby inter-
rupted.
Remedy
–
Check wiring
Содержание PROFINET CPX-AP-A-PN-M12
Страница 1: ...CPX AP A PN M12 PROFINET interface Operating instruc tions 8160756 2022 07 8160758...
Страница 27: ......