Festo — CPX-AP-A-EC-M12 — 2022-07
Diagnostics and fault clearance
ID hex (dec)
Message
Description
08 | 01 | 0134
(134283572)
AP master toggle bit
error
Diag-
nostic
status
Error
08 | 01 | 01A4
(134283684)
Device variant mis-
match
The currently set device variant does not match with the
system configuration. The device variant is automatically
set to the system configuration.
Remedy
–
In case that the device variant is not set
automatically, set the device variant to the
value configured for the system.
Diag-
nostic
status
Information
08 | 01 | 01AD
(134283693)
System state change
to OPERATION failed
The AP device did not change the system state from CON-
FIGURATION to OPERATION.
Remedy
–
Restart system
–
Update firmware to latest version
–
Contact Festo service
Diag-
nostic
status
Warning
08 | 01 | 01C4
(134283716)
AP Module(s)
detected
One or more new AP module(s) were detected in the
system.
Remedy
–
None
Diag-
nostic
status
Information
08 | 01 | 01FF
(134283775)
Device not ready
A device is delaying the startup excessively long.
Remedy
–
Contact Festo Support
Diag-
nostic
status
Error
08 | 01 | 0215
(134283797)
Device forced to com-
munication loopback
The device was forced by the master to set the loopback
on the communication port, due to commnuication errors.
Communication to subsequent modules is thereby inter-
rupted.
Remedy
–
Check wiring