Festo — CPX-AP-A-EC-M12 — 2022-07
Diagnostics and fault clearance
25
ID hex (dec)
Message
Description
08 | 01 | 0127
(134283559)
AP Module Discon-
nected
Diag-
nostic
status
Error
08 | 01 | 0130
(134283568)
AP module process
data output watchdog
timed out
The process data watchdog for the outputs timed out in
the module
Remedy
–
Restart AP master.
–
Check wiring.
Diag-
nostic
status
Error
08 | 01 | 0131
(134283569)
AP module process
data input watchdog
timed out
The process data watchdog for the inputs timed out in the
module
Remedy
–
Restart AP master.
–
Check wiring.
Diag-
nostic
status
Error
08 | 01 | 0132
(134283570)
AP master process
data output watchdog
timed out
The process data watchdog for the outputs timed out in
the master
Remedy
–
Adjust cycle time and watchdog parameter.
–
Restart AP system.
–
Check wiring.
Diag-
nostic
status
Error
08 | 01 | 0133
(134283571)
AP master process
data input watchdog
timed out
The process data watchdog for the inputs timed out in the
master
Remedy
–
Adjust cycle time and watchdog parameter.
–
Restart AP system.
–
Check wiring.
Diag-
nostic
status
Error
08 | 01 | 0134
(134283572)
AP master toggle bit
error
A module did not mirror the toggle bit in the process data
Remedy
–
Adjust cycle time and toggle timeout
parameter.
–
Restart AP system.
–
Check wiring.