Service

NOTICE!

Accumulation of heat due to reduced air supply to electronics.

Keep the ventilation slots free and regularly remove contamination.

12

Diagnostics and fault clearance

12.1

Diagnostics options

Various options are available for diagnosing errors:

Internal system diagnostics

LED indicators on the product

12.2

Internal system diagnostics

The internal system diagnostics is described in the “Description of automation
system CPX-E” 

è

 1.1 Further applicable documents.

12.3

LED indicators

The module-specific LED indicators are described in this document.
The system-specific LED indicators are described in the documentation for the
automation system CPX-E 

è

 1.1 Further applicable documents.

Module error [

P

]

1)

LED
(red)

Meaning

Remedy

General error/module error

Check the devices, power supplies and
installation.
Check parameterisation and adjust.

Lit

Channel error/error between module and
device

Check the line and connections.
Check and adapt the address space.
Check device.

Off

System-internal communication OK
No module error

1) Flashes once briefly at the initialisation of the automation system CPX-E.

Tab. 9 Module error

IO-Link mode (IOL) [X0] 

 [X3]

LED
(green)

Meaning

Remedy

Lit

IO-Link communication exists without
channel error

Flashes

IO-Link channel diagnosis
Device indicates an event or connection to
device interrupted

Read out the event code through the
“Device error code” and perform the cor-
responding remedial measures.
Further information:
"Description of IO Link master module"

è

 1.1 Further applicable documents.

Off

No IO-Link communication exists

Tab. 10 IO-Link mode (IOL) [X0] ... [X3]

Standard IO mode (SIO) [X0] 

 [X3]

LED
(yellow)

Meaning

Remedy

Lit

Process signal = 1

Off

Process signal = 0

Tab. 11 Standard IO mode (SIO) [X0] ... [X3]

Load voltage supply U

OUT

 [PL]

LED
(green)

Meaning

Remedy

Lit

Load voltage supply U

OUT

 exists

Load voltage supply U

OUT

 [PL]

LED
(green)

Meaning

Remedy

Flashes

Undervoltage of the load voltage supply
U

OUT

 on at least one device

Off

Load voltage supply U

OUT

 not present or

undervoltage

Check the load voltage supply U

OUT

.

Tab. 12 Load voltage supply [PL]

13

Disposal

ENVIRONMENT!

Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations 

è

 www.festo.com/sp.

14

Technical Data

General technical data

CPX-E-4IOL

CPX-E-4IOL-EX1E

General technical data
Automation system CPX-E

Description of automation system CPX-E

è

 1.1 Further applicable documents

Dimensions
(length × width × height)

1)

[mm]

124.3 × 18.9 × 76.6

Product weight

2)

[g]

96

Mounting position

Vertical/horizontal

Ambient temperature

[°C]

–5 … +60 (–5 … +50)

3)

Storage temperature

[°C]

–20 … +70

Humidity (non-condensing)

[%]

0 … 95

Assigned address space
(inputs/outputs)

4)

[Bytes]

32/32 (max.)

Degree of protection in accordance with
EN 60529

IP20
The degree of protection is not UL-tested.

Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)

through the use of PELV circuits
(protected extra-low voltage)

Electromagnetic compatibility

To EN 61000-6-2/-4

to EN 61000-6-2/-4 and
NE 21

Module code (CPX-E-specific)

174

Submodule code (CPX-E-specific)

If all ports 1 … 4 are activated by
DIL switches

è

 Tab. 5 DIL switch

4

104

If only ports 1 and 2 are activated by
DIL switches

è

 Tab. 5 DIL switch

2

102

If only port 1 is activated by
DIL switches

è

 Tab. 5 DIL switch

1

101

Module identification

If all ports 1 … 4 are activated by
DIL switches

è

 Tab. 5 DIL switch

E-4IOL

E-4IOL-EX1E

If only ports 1 and 2 are activated by
DIL switches

è

 Tab. 5 DIL switch

E-2IOL

E-2IOL-EX1E

If only port 1 is activated by
DIL switches

è

 Tab. 5 DIL switch

E-1IOL

E-1IOL-EX1E

1) not including linking element
2) Including linking element
3) for horizontal mounting position
4) dependent on the setting of the DIL switches

Tab. 13 General Technical Data

Power supply

CPX-E-4IOL

CPX-E-4IOL-EX1E

Operating power supply
U

EL/SEN

[V DC

24 

_

 25%

Intrinsic current consumption
at nominal operating voltage
24 V from U

EL/SEN1)

[mA]

50

Mains buffering time U

EL/SEN

[ms]

10

20

Load voltage supply

OUT

[V DC]

24 

_

 25%

Capacitive load U

OUT

[nF]

363

Undervoltage identification U

EL/SEN

Trigger level

[V DC]

17

Hysteresis

[V DC]

0.5

1) without connected devices

Tab. 14 Power Supply