11
Service
NOTICE!
Accumulation of heat due to reduced air supply to electronics.
•
Keep the ventilation slots free and regularly remove contamination.
12
Diagnostics and fault clearance
12.1
Diagnostics options
Various options are available for diagnosing errors:
–
Internal system diagnostics
–
LED indicators on the product
12.2
Internal system diagnostics
The internal system diagnostics is described in the “Description of automation
system CPX-E”
è
1.1 Further applicable documents.
12.3
LED indicators
The module-specific LED indicators are described in this document.
The system-specific LED indicators are described in the documentation for the
automation system CPX-E
è
1.1 Further applicable documents.
Module error [
P
]
1)
LED
(red)
Meaning
Remedy
General error/module error
Check the devices, power supplies and
installation.
Check parameterisation and adjust.
Lit
Channel error/error between module and
device
Check the line and connections.
Check and adapt the address space.
Check device.
Off
System-internal communication OK
No module error
–
1) Flashes once briefly at the initialisation of the automation system CPX-E.
Tab. 9 Module error
IO-Link mode (IOL) [X0]
…
[X3]
LED
(green)
Meaning
Remedy
Lit
IO-Link communication exists without
channel error
–
Flashes
IO-Link channel diagnosis
Device indicates an event or connection to
device interrupted
Read out the event code through the
“Device error code” and perform the cor-
responding remedial measures.
Further information:
"Description of IO Link master module"
è
1.1 Further applicable documents.
Off
No IO-Link communication exists
–
Tab. 10 IO-Link mode (IOL) [X0] ... [X3]
Standard IO mode (SIO) [X0]
…
[X3]
LED
(yellow)
Meaning
Remedy
Lit
Process signal = 1
–
Off
Process signal = 0
–
Tab. 11 Standard IO mode (SIO) [X0] ... [X3]
Load voltage supply U
OUT
[PL]
LED
(green)
Meaning
Remedy
Lit
Load voltage supply U
OUT
exists
–
Load voltage supply U
OUT
[PL]
LED
(green)
Meaning
Remedy
Flashes
Undervoltage of the load voltage supply
U
OUT
on at least one device
Off
Load voltage supply U
OUT
not present or
undervoltage
Check the load voltage supply U
OUT
.
Tab. 12 Load voltage supply [PL]
13
Disposal
ENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations
è
14
Technical Data
General technical data
CPX-E-4IOL
CPX-E-4IOL-EX1E
General technical data
Automation system CPX-E
Description of automation system CPX-E
è
1.1 Further applicable documents
Dimensions
(length × width × height)
1)
[mm]
124.3 × 18.9 × 76.6
Product weight
2)
[g]
96
Mounting position
Vertical/horizontal
Ambient temperature
[°C]
–5 … +60 (–5 … +50)
3)
Storage temperature
[°C]
–20 … +70
Humidity (non-condensing)
[%]
0 … 95
Assigned address space
(inputs/outputs)
4)
[Bytes]
32/32 (max.)
Degree of protection in accordance with
EN 60529
IP20
The degree of protection is not UL-tested.
Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)
through the use of PELV circuits
(protected extra-low voltage)
Electromagnetic compatibility
To EN 61000-6-2/-4
to EN 61000-6-2/-4 and
NE 21
Module code (CPX-E-specific)
174
Submodule code (CPX-E-specific)
If all ports 1 … 4 are activated by
DIL switches
è
4
104
If only ports 1 and 2 are activated by
DIL switches
è
2
102
If only port 1 is activated by
DIL switches
è
1
101
Module identification
If all ports 1 … 4 are activated by
DIL switches
è
E-4IOL
E-4IOL-EX1E
If only ports 1 and 2 are activated by
DIL switches
è
E-2IOL
E-2IOL-EX1E
If only port 1 is activated by
DIL switches
è
E-1IOL
E-1IOL-EX1E
1) not including linking element
2) Including linking element
3) for horizontal mounting position
4) dependent on the setting of the DIL switches
Tab. 13 General Technical Data
Power supply
CPX-E-4IOL
CPX-E-4IOL-EX1E
Operating power supply
U
EL/SEN
[V DC
24
_
25%
Intrinsic current consumption
at nominal operating voltage
24 V from U
EL/SEN1)
[mA]
50
Mains buffering time U
EL/SEN
[ms]
10
20
Load voltage supply
OUT
[V DC]
24
_
25%
Capacitive load U
OUT
[nF]
363
Undervoltage identification U
EL/SEN
Trigger level
[V DC]
17
Hysteresis
[V DC]
0.5
1) without connected devices
Tab. 14 Power Supply