10.4.2
Station status
Station status 1
Bit
Contents
Meaning (bit set)
0
Diag.Station_Non_Existent
The automation system CPX-APis no longer accessible
or not yet accessible.
Possible causes:
–
Operating voltage not applied
–
Data transmission line interrupted or disturbed
1
Diag.Station_Not_Ready
The automation system CPX-APis not yet ready for data
exchange.
2
Diag.Cfg_Fault
The configuration data received from the master do not
agree with the configuration determined by the auto-
mation system CPX-AP.
3
Diag.Ext_Diag
A diagnostics message is pending.
Possible causes:
–
Cable break at input/output module
–
Short circuit/overload at electrical outputs
4
Diag.Not_Supported
The automation system CPX-AP does not support the
requested function.
5
Diag.Invalid_Slave_Response
always 0
(fixed by the automation system CPX-AP)
6
Diag.Prm_Fault
The last parameterisation telegram is faulty.
7
Diag.Master_Lock
always 0
(fixed by the automation system CPX-AP)
Tab. 23 Station status 1
Diagnostics and fault clearance
21
Festo — CPX-AP-I-PB-M12 — 2020-03