9.2
Modbus TCP
9.2.1
Holding register
Register
Length
Access
1)
Name
Description/value
Holding register
0
4096
rw
Outputs
Outputs
5000
4096
ro
Inputs
Inputs
10000
1000
rw
Parameter
Parameter
è
11000
1000
ro
Diagnosis
Diagnostics
12000
1
ro
Module count
Number of modules
14000
2
rw
Timeout
Timeout (default 100 ms)
15000
18500
ro
Module information
Module information
è
Input register
0
4096
ro
Inputs
Inputs
Discrete input
0
32768
ro
Inputs
Inputs
2)
Coils
0
32768
rw
Outputs
Outputs
2)
1) ro = read only; rw = read write
2) dependent on the configuration of the automation system CPX-AP
Tab. 26 Holding register
Sequence for executing a request
Step
Access
Register
Description
1
Write
10000
Module number
2
Write
10001
Parameter ID
3
Write
10002
Parameter instance
4
Write
10004 and
10010 ...
Data length and
Data
5
Write
10003
1 = read or 2 = write
6
Read
10003
up to 16 = done or 4 = error
7
Read
10004 and
10010 ...
Data length and
Data
Tab. 27 Sequence for executing a request
Parameterisation
33