ID hex (dec)
Message
Description
0B
|
08
|
018F
(185074063)
Unsupported Full Dia-
gnostic Image version
Diagnost-
ic status
Error
The diagnostic version is not supported.
Remedy
–
Check and adjust firmware versions of
master and devices.
0B
|
08
|
0190
(185074064)
Unsupported dia-
gnostic version
Diagnost-
ic status
Error
The device description file stored in the device at the fact-
ory is invalid or missing.
Remedy
–
Restart device.
–
Check AP system communication.
–
Check firmware version.
–
In the event of repeated errors, contact
Festo Service.
0B
|
09
|
0128
(185139496)
APDD invalid
Diagnost-
ic status
Error
The start-up device description file stored in the device at
the factory is invalid or missing.
Remedy
–
Restart device.
–
Check AP system communication.
–
Check firmware version.
–
In the event of repeated errors, contact
Festo Service.
0B
|
09
|
0129
(185139497)
Start-up APDD invalid
Diagnost-
ic status
Error
Tab. 19 Diagnostic Messages
Diagnostics and Fault Clearance
25
Festo — CPX-AP-I-EC-M12 — 2019-11