Festo — CPX-4AE-4AA-H — 2021-06b
Product overview
7
Bus node/controller
Function range
Required revision
CPX-FB13 (PROFIBUS)
full HART functionality
from Rev 34
CPX-FB33 (PROFINET IO)
from Rev 34
CPX-M-FB34 (PROFINET IO)
from Rev 33
CPX-M-FB35 (PROFINET IO)
from Rev 33
CPX-FB36 (EtherNet/IP)
from Rev 15
CPX-FB37 (EtherCAT)
from Rev 7
CPX-FB43 (PROFINET IO)
from Rev 45
CPX-(M)-FB44 (PROFINET IO)
from Rev 45
CPX-(M)-FB45 (PROFINET IO)
from Rev 45
CPX-CEC-C1-V3
Package 3.5.12.174
CPX-CEC-S1-V3
Package 3.5.12.174
CPX-CEC-M1-V3
Package 3.5.12.174
CPX-FB11 (DeviceNet)
HART variables can be used in
the process image
from Rev 25
CPX-FB14 (CANopen)
from Rev 30
Tab. 3: Suitable bus nodes/controllers and required revisions
Interlinking block
Manifold block
CPX-P-AB-4XM12-4POL
Manifold block
CPX-P-AB-2XKL-8POL
Metal design
permissible
permissible
Polymer version
not permissible
permissible
Tab. 4: Permissible combination of manifold block and interlinking block
2.3
Training of qualified personnel
Work on the product may only be carried out by qualified personnel who can evaluate the work
and detect dangers. The qualified personnel have skills and experience in dealing with electrical
(open-loop) control technology.
3
Additional information
–
Contact the regional Festo contact if you have technical problems
–
Accessories and spare parts
4
Product overview
4.1
Function
The analogue module with HART functionality provides analogue current inputs and current outputs
and enables the recording and further processing of analogue current signals.
–
4 analogue current channels, configurable as input or output by DIL switch
–
LED indicators for status and fault indications on the module