CMSX-...-C-U-F1-...
Festo – CMSX-...-C-U-F1-... – 1506a English
57
12
Fault clearance
Malfunction
Possible cause
Remedy
Error in positioning
Initialization has not been
executed
Execute initialization
(
è
Fast-switching valves of the CMSX
defective
Send the device to the Festo repair
service
Mechanical connection between
CMSX and drive defective
Restore mechanical connection
(
è
tighten coupling, if necessary;
replace defective coupling
Failure of the compressed air
supply or unstable compressed air
supply
Establish compressed air supply;
minimise pressure fluctuations
(
è
Drive tends to overswings
or permanent oscillations
Controller parameter incorrectly
set; small drives may require flow
control valves
Correct setting (
è
reduce speed with flow control
valves
The process valve does
not take on the correct
position if there is an
operating voltage failure.
Tubing connection between CMSX
and semi-rotary drive defective
Correct tubing connection between
CMSX and semi-rotary drive
(
è
The device does not react
to setpoint value
specifications.
Compressed air supply is lacking
Establish compressed air supply
Display shows the Sensor Error
message, as the sensing range of
the sensor has been exceeded.
Correct alignment and mechanical
connection between CMSX and
semi-rotary drive (
è
The device is in the “Controller
stopped” operating status. The
controller is inactive.
Start operation in order to activate
the controller (
è
The device reacts to a signal at the
control port D-IN.
Deactivate control signal at the
control port D-IN or correct
parameterisation (
è
The device does not react
to analogue setpoint value
specification.
Setpoint input is inactive
Activate desired setpoint input
(
è
The device is operated in the
manual override operating mode.
Activate automatic mode
(
è
The semi-rotary drive runs
to an end position, even
though another setpoint
value is specified.
The operating voltage supply is
outside the permissible range or
switched off. The fast-switching
valves take on the neutral position
(
è
Check operating voltage supply
(
è
Tab. 26