Setting parameters
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
97
Object 6075
h
: motor_rated_current
This value can be taken from the motor rating plate and is entered in milliamperes. The effective value
(RMS) is always assumed. No current can be specified above the motor controller nominal current
(6510
h
_40
h
: nominal_current).
Index
6075
h
Name
motor_rated_current
Object Code
VAR
Data Type
UINT32
Access
rw
PDO mapping
yes
Units
mA
Value Range
0 … nominal_current
Default Value
296
If the object 6075
h
(motor_rated_current) is written over with a new value, the object
6073
h
(max_current) must always be parametrised again.
Object 6073
h
: max_current
As a rule, servo motors may be overloaded for a certain time period. With this object, the maximum
permissible motor current is set as a factor. It refers to the nominal motor current (object 6075
h
: mo
tor_rated_current) and is set in thousandths. The range of values is limited upward by the maximum
controller current (object 6510
h
_41
h
: peak_current). Many motors may be overloaded briefly by a
factor of 4. In this case, the value 4000 is written into this object.
The object 6073h (max_current) may only be written over if the object 6075h
(motor_rated_current) was previously overwritten.
Index
6073
h
Name
max_current
Object Code
VAR
Data Type
UINT16
Access
rw
PDO mapping
yes
Units
per thousands of rated current
Value Range
–
Default Value
2023