Setting parameters
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
129
5.13
Digital inputs and outputs
Overview
All digital inputs of the motor controller can be read via the CAN bus, and almost all digital outputs can
be set as desired. Moreover, status messages can be assigned to the digital outputs of the motor con
troller.
Description of the objects
Objects treated in this chapter
Index
Object
Name
Type
Attr.
60FD
h
VAR
digital_inputs
UINT32
ro
60FE
h
ARRAY
digital_outputs
UINT32
rw
2420
h
RECORD
digital_output_state_mapping
ro
2420
h
_01
h
VAR
dig_out_state_mapp_dout_1
UINT8
rw
2420
h
_02
h
VAR
dig_out_state_mapp_dout_2
UINT8
rw
2420
h
_03
h
VAR
dig_out_state_mapp_dout_3
UINT8
rw
Object 60FD
h
: digital_inputs
The digital inputs can be read via the object 60FDh:
Index
60Fd
h
Name
digital_inputs
Object Code
VAR
Data Type
UINT32
Access
ro
PDO mapping
yes
Units
–
Value Range
according to the following table
Default Value
0
Bit
Value
Meaning
0
00000001
h
Negative limit switch
1
00000002
h
Positive limit switch
2
00000004
h
Reference switch
3
00000008
h
Interlock (controller or output stage enable missing)
16 … 23
00FF0000
h
Digital inputs of the CAMC-D-8E8A
24 … 27
0F000000
h
DIN0 … DIN3
28
10000000
h
DIN 8
29
20000000
h
DIN 9