REMOTE CONTROLLER - SERVICE MENU
8.16 Test run
TEST RUN is used to check correct operation of the valves, air purge, circulation
pump operation, cooling, heating and domestic water heating. To enter test run, go
to MENU> FOR SERVICEMAN> TEST RUN. Press OK.
11 TEST RUN
Activate the settings and
activate “TEST RUN”?
SCROLL
CONFIRM
OK
NO
YES
fig. 141 -
If YES is selected, the following page is displayed:
11 TEST RUN
AIR PURGE
CIRCULATION PUMP RUNNING
COOL MODE RUNNING
HEAT MODE RUNNING
DHW MODE RUNNING
11.1 POINT CHECK
SCROLL
ENTER
OK
fig. 142 -
Use ▼ ▲ to scroll to the mode you want to run and press OK. The unit will run
as selected.
If 11.1 POINT CHECK is selected, the following page will not be displayed:
11.1 POINT CHECK
2-WAY VALVE
PUMP1
PUMP0
PUMP0
PUMPSOLAR
3-WAY VALVE
OFF
OFF
OFF
OFF
OFF
OFF
SCROLL
ON/OFF
ON/OFF
11.1 PIONT CHECK
BACKUP HEATER1
BACKUP HEATER2
TANK HEATER
PUMPDHW
OFF
OFF
OFF
OFF
SCROLL
ON/OFF
ON/OFF
fig. 143 -
11.1 POINT CHECK
2-WAY VALVE
PUMP1
PUMP0
PUMP0
PUMPSOLAR
3-WAY VALVE
OFF
OFF
OFF
OFF
OFF
OFF
SCROLL
ON/OFF
ON/OFF
11.1 PIONT CHECK
BACKUP HEATER1
BACKUP HEATER2
TANK HEATER
PUMPDHW
OFF
OFF
OFF
OFF
SCROLL
ON/OFF
ON/OFF
fig. 144 -
Use ▼ ▲ to scroll to the components you want to check and press ON/OFF. For
example, when 3-WAY VALVE is selected and ON/OFF is pressed, if the 3-way
valve is open/close, then the operation of 3-way valve is normal, and so are other
components.
If you select AIR PURGE and OK is pressed, the page will displayed as follows:
11 TEST RUN
Test run is on.
Air purge is on.
CONFIRM
OK
fig. 145 -
When in air purge mode, the 3-way valve will open, the 2-way valve will close.
60s later the pump in the unit (PUMPI) will operate for 10min during which the
flow switch will not work. After the pump stops, the 3-way valve will close and the
2-way valve will open. 60s later both the PUMPI and PUMPO will operate until the
next command is received.
When CIRCULATION PUMP RUNNING is selected, the page will displayed as
follows:
11 TEST RUN
Test run is on.
Circulation pump is on.
CONFIRM
OK
fig. 146 -
When selecting COOL MODE is OK, the unit is forced to work in COOL MODE and
the page opposite appears on the display.
During this function the water setpoint (T1S) is equal to 7 ° C. The unit continues to
operate until the setpoint is satisfied or until the next command is received.
11 MODO TEST
Modo test attivo.
Modo freddo attivo.
Temperatura uscita acqua 15
°C.
CONFERMA
OK
fig. 147 -
Содержание OMNIA HYBRID C
Страница 34: ...34 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU 7 2 Menu structure ...
Страница 35: ...35 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU DHW mode is setting OFF ...
Страница 36: ...36 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU ...
Страница 51: ...51 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU ...
Страница 52: ...52 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU REMOTE CONTROLLER FOR SERVICEMAN MENU ...
Страница 53: ...53 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU U ...
Страница 100: ...100 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Principle scheme ...
Страница 101: ...101 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Electronic heat pump board ...
Страница 102: ...102 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Wiring board ...
Страница 113: ...113 EN Cod 3541T090 Rev 00 06 2019 ...
Страница 114: ...114 EN Cod 3541T090 Rev 00 06 2019 ...
Страница 115: ...115 EN Cod 3541T090 Rev 00 06 2019 ...