background image

EXTREMA

22

EN

cod. 3540S060  -  04/2010  (Rev. 00)

3.2 Start-up

B

Checks to be made at first lighting, and after all maintenance operations that involved disconnection from the
systems or an operation on safety devices or parts of the boiler:

Before lighting the boiler

Open any on-off valves between the boiler and the systems.

Check the tightness of the gas system, proceeding with caution and using a soap and water solution to detect any
leaks in connections.

Check correct prefilling of the expansion tank (ref. sec. 4.4 Technical data table).

Fill the water system and make sure all air contained in the boiler and the system has been vented, by opening the
air vent valve on the boiler and any vent valves on the system. 

Fill the condensate trap and check correct connection of the condensate elimination system.

Make sure there are no water leaks in the system, DHW circuits, connections or boiler.

Check correct connection of the electrical system and efficiency of the earthing system

Make sure the gas pressure value for heating is that required.

Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.

Checks during operation

Turn the unit on as described in sec. 1.3 Lighting and turning off.

Make sure the fuel circuit and water systems are tight.

Check the efficiency of the flue exhaust and air ducts while the boiler is working.

Check the correct tightness and functionality of the condensate elimination system and trap.

Make sure the water is circulating properly between the boiler and the systems.

Make sure the gas valve modulates correctly in the heating and domestic hot water production phases.

Check proper boiler lighting by doing several tests, turning it on and off with the room thermostat or remote control.

Using a combustion analyser connected to the boiler fume outlet, check that the CO

2

 content in the fumes, with the

boiler operating at max. and min. output, corresponds to that given in the technical data table for the corresponding
type of gas.
(Because the combustion for this appliance has been checked, adjusted and preset at the factory, it is only neces-
sary to undertake a further combustion check if there are operating performance  difficulties or the boiler has been
converted or if essential components have been replaced).

Make sure the gas rate indicated on the meter matches that given in the technical data table on sec. 4.4 Technical
data table.

Check the correct programming of the parameters and carry out any necessary customization (compensation curve,
power, temperatures, etc.).
(As the  parameters for each boiler are factory set, there is no requirement to recheck paramters at the time of com-
missioning unless a gas conversion has been undertaken.)

3.3 Commisioning instructions

General

PLEASE NOTE:

 The combustion for this appliance has been checked, adjusted and preset at the factory for operation

on the gas type defined on the appliance data plate.

Having checked:

That the boiler has been installed in accordance with these instructions,

The integrity of the flue system and the flue seals.

The integrity of the boiler combustion circuit and the relevant seals.

Test mode

Proceed to put the boiler into operation as follows:

1. To operate the boiler in test mode, press the CH keys together for 5 seconds (see fig. 30)
2. The boiler lights at percentage ignition (40% dependant on model)

Содержание Lamborghini EXTREMA 30 C

Страница 1: ...6 cod 3540S060 04 2010 Rev 00 EXTREMA C INSTRUCTIONS FOR USE INSTALLATION AND MAINTENENCE FOR THE UNITED KINGDOM AND EIRE...

Страница 2: ...the manufacturer s instructions Before carrying out any cleaning or maintenance oper ation DISCONNECT AND ISOLATE the boiler from the electrical power supply In case the unit breaks down and or funct...

Страница 3: ...nnection 13 2 5 Electrical connections 13 2 6 Flue system 14 2 7 Condensate drain connection 19 3 Service and maintenance 21 3 1 Adjustments 21 3 2 Start up 22 3 3 Commisioning instructions 22 3 4 Rou...

Страница 4: ...C 1 2 Control panel fig 1 Control panel Key 1 DHW temperature setting decrease button 2 DHW temperature setting increase button 3 Heating system temperature setting decrease button 4 Heating system te...

Страница 5: ...ot water DHW fig 3 A DHW demand generated by drawing domestic hot water is indicated by flashing of the hot water symbol details 12 and 13 of fig 1 The display detail 14 fig 1 shows the actual hot wat...

Страница 6: ...g system air venting cycle During the first 5 seconds the display will also show the PCB software version Open the gas cock ahead of the boiler When the message FH disappears the boiler is ready to op...

Страница 7: ...0 DHW temperature adjustment fig 11 Operate the DHW buttons details 1 and 2 fig 1 to adjust the temperature from a min of 40 C to a max of 55 C fig 11 Room temperature adjustment with optional room th...

Страница 8: ...s details 3 4 fig 1 The boiler must be regulated at the time of installation by qualified personnel Possible adjustments can in any case be made by the user to improve comfort Compensation curve and c...

Страница 9: ...the display by FH 20 30 40 50 60 70 80 90 85 20 10 0 10 20 1 2 3 4 5 6 8 9 10 7 Maximum boiler flow temperature Outside Air Temperature 20 30 40 50 60 70 80 90 85 20 10 0 10 20 1 2 3 4 5 6 8 9 10 7 2...

Страница 10: ...ter By Laws Great Britain For Northern Ireland the relevant laws in force must be observed Safe handling of materials Pay attention when handling the boiler insulation panels because the material they...

Страница 11: ...the building s heat requirement accord ing to the current regulations To ensure proper operation and long boiler life the plumbing system must be adequately sized and complete with all the necessary a...

Страница 12: ...ing F System return cock 3 4 System filling Replenishing water It is necessary to provide for replenishing of the water lost by the sealed system Refer to standard BS6798 for the methods of filling an...

Страница 13: ...nnections The unit must be installed in conformity with current national and local regulations Connection to the electrical grid B The unit s electrical safety is only guaranteed when correctly connec...

Страница 14: ...s 1 2 or 7 8 If a remote timer control and room thermostat are required then these must be connected in series 2 6 Flue system This unit is a C type with sealed chamber and forced draught with air inl...

Страница 15: ...c pipe used 4 If necessary cut the terminal length to size ensuring that the external pipe protrudes from the wall by between 10 and 60 mm Remove the cutting burrs 5 Connect flue to the boiler positio...

Страница 16: ...eduction indicated in the table For example a 60 100 duct comprising a 90 bend 1 horizontal metre has a total equivalent length of 2 metres Table 1 Max length coaxial ducts Connection with separate pi...

Страница 17: ...equivalent metres of every component according to the instal lation position 3 Check that the sum total of losses is less than or equal to the maximum permissible length in table 2 Table 2 Max length...

Страница 18: ...ening e g door window with access to the home 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm O From the wall on which the terminal...

Страница 19: ...h no constrictions Have the ducts conveying the hot fumes at a suitable distance or separately from combustible materials Be connected to just one unit per floor for not more than 6 units 8 if there i...

Страница 20: ...to reduce the length of the condensate drain pipes and run them on the inside as much as possible before going to the outside It may also be necessary to insulate the condensate pipe or apply a trace...

Страница 21: ...htness of the connection 5 Apply the label contained in the conversion kit near the dataplate 6 Refit the casing 7 Modify the parameter for the type of gas put the boiler in standby mode press the DHW...

Страница 22: ...correctly in the heating and domestic hot water production phases Check proper boiler lighting by doing several tests turning it on and off with the room thermostat or remote control Using a combustio...

Страница 23: ...e Set up the boiler to operate at maximum rate as de scribed in sec Test mode of cap 3 3 With the boiler operating in the maximum rate condi tion check that the operational working gas pressure at the...

Страница 24: ...rs in accordance with BS 7967 Parts 1 to 4 Periodical check To keep the unit working properly over time it is necessary to have qualified personnel make an annual check that in cludes the following te...

Страница 25: ...2 Wait 10 minutes to allow the boiler to stabilize 3 Now adjust the Throttle setting fig 35 screw A until the CO2 is at the correct SETTING LEVEL see table 4 confirm that the CO CO2 ratio is within l...

Страница 26: ...A to restore operation press the RESET button detail 8 fig 1 for 1 second or RESET on the optional remote timer control if installed if the boiler fails to start it is necessary to firstly eliminate...

Страница 27: ...ce the sensor Wiring shorted Wiring disconnected F15 Fan fault No 230V power supply Check the wiring of the 3 pin connector Tachometric signal interrupted Check the wiring of the 5 pin connector Fan d...

Страница 28: ...Dimensions and connections fig 36 Dimensions and connections 1 Heating system delivery 2 Domestic hot water outlet 3 Gas inlet 4 Cold water inlet 5 Heating system return 6 Safety valve drain 7 Condens...

Страница 29: ...ulating pump 36 Automatic air vent 37 Cold water inlet filter 39 Flow regulator 42 DHW temperature probe 44 Gas valve 56 Expansion tank 82 Detection electrode 95 Diverter valve 136 Flow meter 161 Cond...

Страница 30: ...mp 36 Automatic air vent 37 Cold water inlet filter 42 DHW temperature probe 44 Gas valve 56 Expansion tank 95 Diverter valve 136 Flow meter 154 Condensate outlet pipe 161 Condensing heat exchanger 18...

Страница 31: ...ar 20 20 Maximum DHW production Dt 35 C l min 12 0 15 2 Max gas delivery G20 m3 h 3 1 3 92 Min gas delivery G20 m3 h 0 61 0 74 Gas supply pressure G31 mbar 37 37 Max gas delivery G31 kg h 2 29 2 9 Min...

Страница 32: ...oiler pressure losses 1 Circulating pump min speed 2 Circulating pump max speed Circulating pumps head pressure losses model EXTREMA 38 C fig 40 A Boiler pressure losses 1 Circulating pump min speed 2...

Страница 33: ...mostat not supplied 72B Second room thermostat not supplied 82 Detection electrode 95 Diverter valve 136 Flow meter 138 External probe 139 Remote timer control 186 Return sensor 188 Ignition electrode...

Страница 34: ...ED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE ft3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET TEMPERATURE C HOT WATER OUTLET TEMPERATURE C WATER FLOW RATE lts...

Страница 35: ...ARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No CO...

Страница 36: ...you require a Service Engineer to visit call our Service Centre on 0871 559 2944 Calls to these numbers are charged at 8 pence per minute from BT landlines Calls from mobile networks may be considerab...

Отзывы: