background image

FORCE W

133

EN

cod. 3541Q760  -  Rev. 00  -  01/2019

1.3 Lighting and shutdown

Boiler lighting

Press the On/Off button (detail 14 - fig. 1).

fig. 7 - Boiler lighting

Press the contextual button 1 to select the language, confirming it by pressing "OK".
Press the contextual button 3 to stop FH mode.
If none of the two selections described above is made, proceed as follows.

For the following 300 seconds the display will show FH which identifies the heating system air venting cycle.

The display also shows the firmware version of the cards.

Open the gas cock ahead of the boiler.

When the message FH disappears, the boiler is ready to operate automatically in case of a room thermostat demand.

Settings

Contrast adjustment

To adjust the display contrast, press the 

contextual button 2

 and the 

OK button together

. Then press the button ref.

5 of fig. 1 to increase the contrast or the button ref. 7 of fig. 1 to decrease it.

Setting the Date and Time

Reach the screen shown in fig. 8, navigating in the menu and following the path "USER MENU 

 “Settings” 

 "Date

Setting”. Press the navigation buttons 5 and 7 to select the value and modify it with the contextual buttons 1 and 2. Con-
firm with the OK button.

fig. 8 - Setting the Date

Display v.01

Burner Controller 1 v.01

to confirm

Set date

24

  /  09

2013

to select

5

7

1

2

Содержание FORCE W

Страница 1: ...cod 3541Q760 Rev 00 01 2019 cod 3541Q760 Rev 00 01 2019 FORCE W 4 1 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FORCE W...

Страница 2: ...the boiler so that it can be con sulted by the new owner and or installer Installation and maintenance must be carried out by professionally qualified personnel accor ding to current regulations and t...

Страница 3: ...connections 144 2 4 Gas connection 159 2 5 Electrical connections 159 2 6 Fume ducts 161 2 7 Condensate drain connection 162 3 Service and maintenance 163 3 1 Adjustments 163 3 2 Commissioning 169 3 3...

Страница 4: ...ystem The boiler body consists of an aluminum tube exchanger and a premix burner in steel equipped with electronic igni tion and ionization flame control a modulating speed fan and a modulating gas va...

Страница 5: ...to navigate among the various menus imple mented in the control panel Menu structure From the main screen Home press the Main menu button detail 12 fig 1 Access the User menu by pressing the contextua...

Страница 6: ...ction on page 140 MAINTENANCE Test mode Test mode See fig 58 Gas Type Selection See fig 55 Cascade Test Mode Service Information See Service Information on page 140 Service Intervention Date See Servi...

Страница 7: ...there will be no de livery of domestic hot water The hot water tank can be deactivated by the user ECO mode by pressing the eco comfort button detail 10 fig 1 In ECO mode the display activates the sy...

Страница 8: ...Heating circulating pump ON OFF Heating 3 way valve ON OFF DHW 3 way valve ON OFF Standby time ON OFF T Delta protection ON OFF Flame Supervisor ON OFF Heating sensor1 C Safety sensor C Return sensor...

Страница 9: ...ead of the boiler When the message FH disappears the boiler is ready to operate automatically in case of a room thermostat demand Settings Contrast adjustment To adjust the display contrast press the...

Страница 10: ...tion system remains activated To relight the boiler press the contextual button again The boiler will be immediately ready to operate whenever domestic hot water is drawn with optional hot water tank...

Страница 11: ...tank remains activated The frost protection system remains activated To deactivate Summer mode press the button detail 9 fig 1 again for 1 second fig 11 Summer Heating temperature adjustment Access th...

Страница 12: ...Temp to vary the temperature from a minimum of 10 C to a maximum of 65 C Confirm with the OK button fig 14 B The boiler is sold with time program not activated Therefore if requested this is the setpo...

Страница 13: ...at the set Heating DHW fig 12 fig 14 Adjustment Tem perature In case of a Heating DHW demand the boiler works at the Reduced Adjustment Temperature The Reduced tem perature is obtained by subtracting...

Страница 14: ...buttons 1 and 2 to set the work mode during the first time band fig 20 fig 20 Then press the navigation button 7 to set if necessary the next time bands fig 21 fig 22 and fig 23 fig 21 to confirm Sch...

Страница 15: ...of days to be programmed fig 17 The same procedure can therefore be followed to complete the desired weekly program fig 24 To program the next day in the same way select Copy to next day and press OK...

Страница 16: ...is programmed but not yet active The Holiday function is in progress The boiler will behave as if Summer mode and Economy mode were active with optional hot water tank installed The frost protection...

Страница 17: ...tment temperature becomes the maximum system delivery temperature It is advisable to set a maximum value to allow system adjustment throughout its useful operating range The boiler must be adjusted at...

Страница 18: ...that given in table 1 Table 1 Heating temperature adjustment The adjustment can be made from the Remote Timer Control menu and the boiler control panel DHW temperature adjustment with optional hot wat...

Страница 19: ...ox 1 0 bar If the system pressure falls to values below minimum the boiler card will activate fault 37 and the number of the module fig 30 fig 30 Module 1 insufficient system pressure fault A Once the...

Страница 20: ...y established by calculating the building s heat requirement according to current regulations The system must be provided with all the components for correct and regular operation In par ticular provi...

Страница 21: ...on the circulating pump model installed Constant Head Dp c setting fig 33 The circulating pump head will remain constant with the decrease in flow rate required by the system This setting is optimum f...

Страница 22: ...and the proliferation of bacterial or microbial masses in low temperature systems The water contained in the system must be checked periodically at least twice a year during the seasons of use as requ...

Страница 23: ...mechani cal filter in the loading circuit and a sludge remover de aerator in the system Antifreeze system antifreeze fluids additives and inhibitors The boiler is equipped with an antifreeze system t...

Страница 24: ...valve in the open position the boiler exchanger is connected to the de livery manifold and in the closed position through the third way the exchanger communicates with the atmos pheric discharge mani...

Страница 25: ...textual button 2 detail 2 fig 1 fig 36 Enter the code 4 1 8 with contextual buttons 1 and 2 Confirm each number with the OK button fig 37 Press the OK button to access the Parameters Menu fig 38 Acces...

Страница 26: ...t is necessary to purchase the external probe accessory code 013018X0 72 1st zone direct room thermostat a 1st zone direct 72b 2nd zone direct room thermostat b 2nd zone direct 138 External probe M De...

Страница 27: ...72 to manage the request of the 1st zone direct 300 Burner On indication voltage free output the example shows the connection of an hour counter at 230Vac 301 Fault indication voltage free contact out...

Страница 28: ...ig 44 Legend 72 1st zone direct room thermostat a 1st zone direct 130 Hot water tank circulating pump b Hot water tank circuit 138 External probe M Delivery 155 Hot water tank probe R Return 300 Legio...

Страница 29: ...obe accessory code 013018X0 If a hot water tank probe not supplied is used it is necessary to purchase the NTC probe accessory code 1KWMA11W 2 mt or code 043005X0 5 mt If a hot water tank thermostat n...

Страница 30: ...wn in the wiring diagram Then configure the controller as described in the specific section fig 46 Legend 32 Heating circulating pump a 1st zone direct 72 1st zone direct room thermostat b Hot water t...

Страница 31: ...essary to purchase the NTC probe accessory code 1KWMA11W 2 mt or code 043005X0 5 mt If a hot water tank thermostat not supplied is used it is necessary to purchase the accessory kit code 013017X0 to b...

Страница 32: ...wn in the wiring diagram Then configure the controller as described in the specific section fig 49 130 d 155 300 a b c 317a 72 139a FZ4B 319a 318a 315a 317b 319b 318b 318c 72 139b 72 139c 315b I M R M...

Страница 33: ...ernal probe 318c 3rd zone direct circulating pump 139a 1st zone mixed Remote Timer Control 319a 1st zone mixed delivery sensor 139b 2nd zone mixed Remote Timer Control 319b 2nd zone mixed delivery sen...

Страница 34: ...free contact output the example shows the connection of a lamp at 230Vac 302 Remote reset input 230Vac the example shows the connection of a double pole switch at 230Vac allowing the resetting of a b...

Страница 35: ...DANGER OF ELECTRIC SHOCK WITH RISK OF INJURY OR DEATH B The unit must be connected to an efficient grounding system in accordance with applicable safety regulations Have the efficiency and suitabilit...

Страница 36: ...neces sary In any case the probe must not be installed near windows doors vents flues or heat sources that could affect the reading fig 51 Inadvisable positioning of external probe Accessing the elect...

Страница 37: ...windows walls ventilation openings etc Manifold ducts and flue must be suitably sized designed and made in compliance with the current regulations They must be made of suitable materials i e resistant...

Страница 38: ...with water 3 Connect the hose from the trap to the condensate drain system B ATTENTION THE UNIT MUST NEVER BE OPERATED WITH THE TRAP EMPTY OTHERWISE THERE IS A DANGER OF SUFFOCATION DUE TO THE EMIS S...

Страница 39: ...s 1 Disconnect the power supply to the boiler 2 Remove the panels 3 Detach the electrical connections from the gas valve controller 4 Undo the fastening screws E and remove the gas valve 5 Replace the...

Страница 40: ...FORCE W 164 EN cod 3541Q760 Rev 00 01 2019 fig 56 Models FORCE W 60 and FORCE W 80 fig 57 Models FORCE W 99 FORCE W 120 and FORCE W 150 G F E F G E...

Страница 41: ...e and not as in a normal heating demand Heating Capacity Adjustment RANGE RATED A This is a RANGE RATED boiler according to EN 483 and can be adjusted to the system s thermal requi rement by setting t...

Страница 42: ...atural Gas b02 Boiler type selection 1 9 7 7 7 7 7 b03 System water pressure protection selection 0 Pressure switch 1 Flow switch 1 sec 2 Flow switch 3 sec 3 Flow switch 5 sec 4 Flow switch 10 sec 5 P...

Страница 43: ...Modulating pump start speed 0 100 75 75 75 75 75 P09 Modulating pump max speed 30 100 100 100 100 100 100 P10 Pump deactivation temperature during Post Circulation 0 100 C 35 35 35 35 35 P11 Pump act...

Страница 44: ...abled OFF OFF OFF OFF OFF P 10 System filling function OFF Disabled ON Enabled OFF OFF OFF OFF OFF P 11 3 way valve selection 2 3 2 or 3 wires 2 2 wires 2 3 2 3 2 3 2 3 2 3 P 12 0 10Vdc Heating OFF vo...

Страница 45: ...he boiler B IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE RISK OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ESCAPING DANGER OF FIRE OR EXPLOSION ALSO THERE MAY BE A RISK OF ELEC TRIC SHOC...

Страница 46: ...ndensate drain traps Check of wiring contacts electrical actuators Check and cleaning of generator air inlets and boiler room air intakes Check and cleaning of fume evacuation duct manifold flue syste...

Страница 47: ...fore carrying out any operation allow these compo nents to cool or alternatively wear appropriate gloves To open the boiler casing 1 Undo the screws A see fig 60 2 Pull the panel B fig 60 Front panel...

Страница 48: ...Check and replace it if necessary A02 Flame present signal with burner off Electrode fault Check the ionization electrode wiring Card fault Check the card A03 Overtemperature pro tection intervention...

Страница 49: ...essure F39 External probe fault Probe damaged or wiring shorted Check the wiring or replace the sensor Probe disconnected after activating the sliding tem perature Reconnect the external probe or disa...

Страница 50: ...drain pipe 155 Hot water tank temperature probe not supplied 186 Return sensor 188 Ignition Ionization electrode 191 Fume temperature sensor 193 Trap 196 Condensate tray 256 Modulating heating circul...

Страница 51: ...Side view fig 63 Top view fig 64 Bottom view model FORCE W 60 and FORCE W 80 fig 65 Bottom view model FORCE W 99 and FORCE W 120 fig 66 Bottom view model FORCE W 150 610 900 460 305 100 305 355 40 31...

Страница 52: ...General view model FORCE W 60 and FORCE W 80 fig 68 General view model FORCE W 99 and FORCE W 120 fig 69 General view model FORCE W 150 44 374 388 186 188 16 191 114 34 193 36 196 44 374 388 186 188 1...

Страница 53: ...FORCE W 177 EN cod 3541Q760 Rev 00 01 2019 4 3 Hydraulic circuit fig 70 Hydraulic circuit 374 388 186 114 34 193 36 196 10 11...

Страница 54: ...fficiency 30 108 6 108 6 108 1 108 1 108 1 NOx emissions class 6 NOx Fume temperature Pmax 80 60 C C 64 70 71 72 73 Fume temperature Pmin 80 60 C C 60 60 60 60 60 Fume temperature Pmax 50 30 C C 44 48...

Страница 55: ...FORCE W 179 EN cod 3541Q760 Rev 00 01 2019 4 5 ErP tables DK KZ t W h h K Z h h h h d ZZK z z EK EK EK h s W W W W W W Y t EK t t t t t t t t t V...

Страница 56: ...FORCE W 180 EN cod 3541Q760 Rev 00 01 2019 DK KZ t W h h K Z h h h h d ZZK z z EK EK EK h s W W W W W W Y t EK t t t t t t t t t V...

Страница 57: ...FORCE W 181 EN cod 3541Q760 Rev 00 01 2019 DK KZ t W h h K Z h h h h d ZZK z z EK EK EK h s W W W W W W Y t EK t t t t t t t t t V...

Страница 58: ...FORCE W 182 EN cod 3541Q760 Rev 00 01 2019 DK KZ t W h h K Z h h h h d ZZK z z EK EK EK h s W W W W W W Y t EK t t t t t t t t t V...

Страница 59: ...FORCE W 183 EN cod 3541Q760 Rev 00 01 2019 DK KZ t W h h K Z h h h h d ZZK z z EK EK EK h s W W W W W W Y t EK t t t t t t t t t V...

Страница 60: ...loss diagram models FORCE W 60 FORCE W 80 FORCE W 99 FORCE W 120 fig 72 Pressure loss diagram models FORCE W 150 A Delivery m3 h B m H2 O FORCE W 6 0 8 0 FORCE W 99 120 0 1 2 3 4 5 6 7 8 9 10 11 10 9...

Страница 61: ...11 12 13 14 15 16 17 2 3 4 5 6 7 8 5 2 186 114 191 16 5 4 3 2 1 1 2 3 37 38 39 40 41 42 43 44 MODBUS 363 256 OUT GND 298 299 138 72B 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 139 72 155 34...

Страница 62: ...2 1 1 2 3 37 38 39 40 41 42 43 44 MODBUS 363 256 OUT GND 298 299 138 72B 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 139 72 155 34 36 35 361 31 33 32 362 32 302 300 301 L N AUX 357 1KW V1 V...

Страница 63: ...Fabbricato in Italia Fabricado en Italia Made in Italy 552 6 S Via 5LWRQGD D 6DQ RQLIDFLR 9HURQD 7 ZZZ IHUUROL FRP...

Отзывы: