4.4 Technical data table
The column on the right gives the abbreviation used on the data plate.
These boilers can work correctly with a minimum flow rate of 0 liters/h.
Model
FORCE W 60
FORCE W 80
FORCE W 99
FORCE W 120
FORCE W 150
PRODUCT IDENTIFICATION CODES
0MDLAAWA
0MDLCAWA
0MDLDAWA
0MDLEAWA
0MDLFAWA
COUNTRIES OF DESTINATION
IT - ES - RO
GAS CATEGORY
II2H3BP
(
IT-ES-RO
)
Max. heating capacity
kW
58.0
74.4
96.6
113.0
143.0
(Q)
Min. heating capacity
kW
15.0
15.0
19.0
19.0
24.0
(Q)
Max. Heat Output in heating (80/60 °C)
kW
57.0
72.9
94.7
110.5
140.0
(P)
Min. Heat Output in heating (80/60 °C)
kW
14.7
14.7
18.7
18.7
23.6
(P)
Max. Heat Output in heating (50/30 °C)
kW
60.8
77.0
100.0
117.0
148.0
(P)
Min. Heat Output in heating (50/30 °C)
kW
16.3
16.3
20.5
20.5
25.9
(P)
Efficiency Pmax (80/60 °C)
%
98.3
98.0
98.0
97.8
97.8
Efficiency Pmin (80/60 °C)
%
98.3
98.3
98.3
98.3
98.3
Efficiency Pmax (50/30 °C)
%
104.8
103.5
103.5
103.5
103.5
Efficiency Pmin (50/30 °C)
%
108.5
108.5
108.0
108.0
108.0
Efficiency 30%
%
108.6
108.6
108.1
108.1
108.1
NOx emissions class
-
6
(NOx)
Fume temperature Pmax (80/60 °C)
°C
64
70
71
72
73
Fume temperature Pmin (80/60 °C)
°C
60
60
60
60
60
Fume temperature Pmax (50/30 °C)
°C
44
48
53
54
54
Fume temperature Pmin (50/30 °C)
°C
30
30
30
30
30
Fume flow rate Pmax
g/s
26
34
44
51
65
Fume flow rate Pmin
g/s
7
7
9
9
11
Gas nozzle G20
Ø
8.5
8.5
9.4
9.4
9.4
Gas supply pressure G20
mbar
20
20
20
20
20
Max. gas flow G20
m
3
/h
6.14
7.87
10.22
11.96
15.13
Min. gas flow G20
m
3
/h
1.59
1.59
2.01
2.01
2.54
CO
2
max G20
%
9.3
9.3
9.3
9.3
9.3
CO
2
min G20
%
8.9
8.9
8.9
8.9
8.9
Gas nozzle G31
Ø
6.4
6.4
7.2
7.2
7.2
Gas supply pressure G31
mbar
37
37
37
37
37
Max. gas flow G31
kg/h
4.51
5.78
7.51
8.78
11.11
Min. gas flow G31
kg/h
1.17
1.17
1.48
1.48
1.86
CO
2
max G31
%
10.5
10.5
10.5
10.5
10.5
CO
2
min G31
%
10.0
10.0
10.0
10.0
10.0
Max. working pressure in heating
bar
6
6
6
6
6
(PMS)
Min. working pressure in heating
bar
0.8
0.8
0.8
0.8
0.8
Max. heating temperature
°C
95
95
95
95
95
(tmax)
Heating water content
liters
4.2
4.2
5.6
5.6
6.7
(H
2
O)
Protection rating
IP
IPX4D
Power supply voltage
V/Hz
230/50
Electrical power input
W
60
93
120
175
250
Empty weight
kg
54
54
63
63
73
Type of unit
B
23
PIN CE
0085