DOMINA F24 N / F28 N / F32 N
20
EN
cod. 3541E094 - Rev. 00 - 06/2014
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler anomaly, the 3 LEDS will indicate the fault code.
There are faults that cause shutdown: in order to restore operation it suffices to press RESET for 1 second (ref. 5 - fig. 1) or perform a RESET on the optional remote timer control if
this is installed. If the boiler fails to start, you must first resolve the fault indicated on the display.
Other faults cause temporary shutdowns which are automatically reset as soon as the value returns within the boiler's normal working range.
Table. 8 - Fault list (Key LEDs
= Off /
= On /
= Fast flashing)
Indications on boiler panel
Indications on Remote Control Fault
Possible cause
Cure
Green
Yellow
Red
A01
No burner ignition
No gas
Check the regular gas flow to the boiler and that the air has
been eliminated from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and that it is correctly
positioned and free of any deposits
Faulty gas valve
Check the gas valve and replace it if necessary
Ignition power too low
Adjust the ignition power
A06
No flame after the ignition phase
Low pressure in the gas system
Check the gas pressure
Burner minimum pressure setting
Check the gas pressures
A02
Flame present signal with burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
F05
Air pressure switch (fails to close con-
tacts within 20 sec. of fan activation)
Air pressure switch contact open
Check the wiring
Faulty air pressure switch wiring
Check the fan
Wrong baffle
Check the pressure switch
Flue not correctly sized or obstructed
Replace the baffle
F07
Air pressure switch (contacts closed on
activation of fan)
Air pressure switch contact open
Check the pressure switch / Fan / Fan socket
Faulty air pressure switch wiring
Check the wiring
Wrong baffle
Make sure the baffle is correct
Flue obstructed or not correctly sized
Check the length of the flues / Clean the flues
F04
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify it if necessary
F37
Low system pressure
System empty
Fill the system
Water pressure switch damaged or not connected
Check the sensor
F10
Delivery sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F43
Exchanger protection intervention (the
LEDs flash alternately)
No system H
2
O circulation
Check the circulating pump
Air in the system
Vent the system
Display off
Faulty card
Card failure
Replace the card
A09
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if necessary
A16
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if necessary
F34
Supply voltage under 140VAC
Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F50
Controller
DBM33
fault
Controller
DBM33
internal error
Check the earth connection and replace the controller if
necessary.
F51
Controller
DBM33
fault
Controller
DBM33
internal error
Check the earth connection and replace the controller if
necessary.
Display off
Card not electrically powered
No power
Check the power supply
Blown fuses
Replace fuses
A03
Overtemperature protection interven-
tion
Heating sensor damaged
Check the correct positioning and operation of the heating
sensor
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
A23
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify it if necessary
A24
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify it if necessary