Table 2. Technical Specification

Model Number

THD-7052

THD-7053

Part Number

70-520000-001

70-530000-001

Detection

Electronic Heat Detector

Electronic Heat Detector

Approvals

cULus, FM, CSFM, MEA-NYC

cULus, FM, CSFM, MEA-NYC

UL Compatibility I.D.

P56FE1

P56FE1

Listed Spacing

      For UL/ULC applications

70 foot (21.3m) centers or 4,900 square feet

(455.2 m 

2

)

70 foot (21.3m) centers or 4,900 square feet

(455.2 m 

2

)

      For FM applications

35 foot (10.7m) centers or 1,225 square feet

(113.8 m 

2

)

35 foot (10.7m) centers or 1,225 square feet

(113.8 m 

2

)

Nominal Sensitivity

135

o

F (57

o

F) w/15

o

F (8.3

o

F) per minute

Rate-of-Rise

135

o

F (57

o

F)

Standby Voltage (VDC)

      Using 2WB

10.2 to 36.8

10.2 to 36.8

      Using 4WRB

16.8 to 36.8

16.8 to 36.8

Maximum Current

       Standby

70 µA

70 µA

       Alarm

100 mA

100 mA

Response Indicators

      Quantity

2 external LEDs

2 external LEDs

      Standby Condition

One flash every 6 seconds

One flash every 6 seconds

      Thermistor Trouble

Double flash every 6 seconds

Double flash every 6 seconds

      Alarm Condition

Steady at full brilliance

Steady at full brilliance

Operating Environment

      Operating Temperature

32

o

 to 100

o

F (0 to 38

o

C)

32

o

 to 100

o

F (0 to 38

o

C)

      Storage Temperature

-20 to 180

o

F (-29

o

 to 82

o

C)

-20 to 180

o

F (-29

o

 to 82

o

C)

      Relative Humidity

0 to 93% Non-condensing

0 to 93% Non-condensing

      Altitude 

Up to 7,500 feet (2,286 m)

Up to 7,500 feet (2,286 m)

Physical Characteristics

      Material and Finish

High-impact, flame-retardant  plastic, off white

High-impact, flame-retardant  plastic, off white

      Weight

35.3 oz. (110g) w/o base

35.3 oz. (110g) w/o base

Dimensions

      Detector Height

1.38 in (35 mm)

1.38 in (35 mm)

      Detector Diameter

3.9 in  (99 mm)

3.9 in  (99 mm)

      Base Height

0.43 in (11mm)

0.43 in (11mm)

      Base Diameter

5.90 in (150 mm)

5.90 in (150 mm)

Содержание THD-7052

Страница 1: ...ecial signal processing techniques verify the presence of smoke before the detector will alarm The detector head is installed into the base with a simple twist lock action A locking feature is provided for vandal resistant se curity Detector base options are available to provide for auxiliary test indication and or control functions Optional bases are available for supplementary 2 wire or 4 wire r...

Страница 2: ...feature Fenwal Model THD 7052 Heat Detectors The contractor shall also furnish and install where indicated on the plans thermistor based electronic Fixed Temperature Fenwal Model THD 7053 Heat Detectors The fixed temperature alarm set point of the THD 7052 and THD 7053 Detectors shall be 135F 57C and the Rate Of Rise detection feature of the THD 7052 shall be rated at 15F 8 3C per minute The combi...

Страница 3: ...100 mA 100 mA Response Indicators Quantity 2 external LEDs 2 external LEDs Standby Condition One flash every 6 seconds One flash every 6 seconds Thermistor Trouble Double flash every 6 seconds Double flash every 6 seconds Alarm Condition Steady at full brilliance Steady at full brilliance Operating Environment Operating Temperature 32o to 100o F 0 to 38o C 32o to 100o F 0 to 38o C Storage Temperat...

Страница 4: ...iary Relay Remote LED Test Capabilities 70 501000 101 4WRB 4 Wire Base with Auxiliary Relay Remote LED Test Capabilities 70 500000 004 2WRM Spare 2 Wire Relay Module 70 500000 102 4WRM Spare 4 Wire Relay Module Detector Accessories 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator with Smoke Detecto...

Отзывы: