FEMA ELECTRÓNICA - Page 2

User’s Manual VIR-30-32

FEMA ELECTRÓNICA - Page 3

Front View and  Connections

DP1 = XX.X

Signal

4 5

3

2

1

+

-

A  B C D

Offset light P1

(±20 points)

P2 Span light

(±50 points)

P3 Span

DP2 = X.XX

Internal Configuration

Offset P4

Signal 

Close Jumpers

4/20 mA 

J1 - J4 - J5 - J6

0/20 mA 

J1 - J4 - J5 - J6

0/10 Vdc 

J3 - J6

0/100 Vdc 

J2 - J6

0/450 Vdc 

J4 - J11

Note .- J12a always closed. J7, 

J10, J12b always open.

J1

Upper Module

seen on solder side

J11

J6

J9 J8 J7

J3

J4

J10

J2

J5

J12a

J12b

Offset Type 

Jumpers

Offset Negative  J8 Closed

(by default)

 

J9 Open

Offset Positive  J8 Open

 

J9 Closed

Power

-

+

Manufacturer  FEMA ELECTRÓNICA, S.A.

 

Pol. Ind. Santiga - Altimira 14

 

E-08210 - Barberà del Vallès  - BARCELONA

 

ESPAÑA - SPAIN 

 

www.fema.es - [email protected]

Series 

VIR-30

Models 

01,03,04,05,06,08,10,15,20,21,32,51 and 90

The  manufacturer  declares  that  the  instruments  indicated 

comply with the directives and rules indicated below.

Directive of electromagnetic compatibility 2004/108/CEE

Directive of low voltage 73/23/CEE

Safety Requirements 61010-1

Equipment “Fixed”, “Permanently connected”

Pollution degree 1, Isolation Double, CAT-II

Emmision requirements

UNE EN 50081-1 (1994)

Immunity requirements

UNE EN 50082-1 (1998)

Barberà del Vallès, April 2010

Daniel Juncà - Quality Manager

CE Declaration of Conformity

INSTALLATION - The power supply circuit must be provided 

with a device that permits disconnection if needed. The power  

supply type and value, and its connection, are printed on the 

labels attached to the instrument. The instrument does not 

have internal protection fuse. To meet safety requirements, 

the installation of a fuse is needed with the values indicated  

below :

 

 

230Vac 

115Vac

 

Fuse 

50 mA 

100 mA

MAINTENANCE  - 

Before  any  operation  of  maitenance, 

adjustment,  repair  or  substitution,  the  instrument  must  be 

unplugged from the power supply. To clean the instrument 

use a humid cloth. Do not use abrasive products (solvents, 

alcohols, ...) to clean the front filter and plastic parts. Do not 

operate  the  instrument  in  places  with  excess  of  humidity, 

smoke, or flammable gas. The instrument is designed to be 

mounted on metalic panel.

IN CASE OF FIRE 1- Disconnect the instrument from the 

power supply. 2- Give alarm according to local rules. 3- Switch 

off air conditioning devices. 4- Attack the fire with carbonic 

snow. Do not use water. In closed areas do not use systems 

with vaporized liquids.

Prescriptions

Mechanical Dimensions (mm)

69

32,5

Panel cut-out

15

60

5

5 max

72

36