14.  Technical specifications

15.  Error codes

Table 7 

Error codes

(Blank)

No display is lightning.

The input current is lower than 2.0 mA or input signal connections 

is inverted.

‘Lo’

The input current is lower than 3.8 mA.

‘h.oVr’

‘Hardware overrange’. 

Input signal is above the maximum readable signal (+22 mA).

‘Err.3’

‘Password error’. 

If ‘password’ function is active, the password code entered is not 

correct.

In case of error, the error code is shown flashing on display. The error 

codes are not visible  while on ‘

configuration mode

’ or in ‘

fast access

’ 

menu.
The error code remains active on display until the problem that caused 

the error is solved. In case of multiple error codes, solve the first problem 

to see the next active error code.

DIGITS AND READING

number of digits

4

type

7 segment led

color

red

digit height

14 mm

maximum reading

9999

minimum reading

-1999

decimal point

configurable X.X.X.X.

overrange / underrange

flash on display

display refresh

2 times / second

acquisition per second

2 acquisitions / second

memory retention

values for maximum and minimum reading are 

stored every 10 minutes

INPUT SIGNAL

signals accepted

4/20 mA (2 wire)

maximum oversignal

30  mA (signals above this value may destroy 

the input circuit)

accuracy

±0.1 % F.S. (±1 count)

thermal drift

<150 ppm / ºC

step response

1500 mSec. (0 % to 99 % signal)

POWER SUPPLY

type

loop powered from the input signal

minimum current to power-up 3.8 mA
voltage drop at terminals

<11 Vdc

wires

0.5 mm

2

 to 2.0 mm

2

 (AWG20 to AWG14)

CONFIGURATION

front keypad

3 push buttons

MECHANICAL

mounting

panel mount

IP front protection

IP50 standard (IP65 optional)

IK impact protection

IK06

connections

plug-in screw terminals (pitch 5.08 mm)

housing material

ABS, polycarbonate (V2)

weight

<110  grams

front size

96 x 48 mm (1/8 DIN standard)

panel cut-out

92 x 44 mm

deep

91  mm including terminals

TEMPERATURE

operation

from 0 to +50 ºC

storage

from -20 to +70 ºC

‘warm-up’ time

15 minutes

PACKAGING

size

116 x 114 x 50 mm

material

cardboard

weight

<150  grams

16. Mechanical dimensions (mm / inch)

Panel 

cut-out

44 mm

96 mm

48 mm

75 mm

16

8

Units

(0.31)

(0.63)

(2.95 in.)

(1.89 in.)

(3.78 in.)

(1.74 in.)

(3.63 in.)

92 mm

Содержание LP4

Страница 1: ...www fema es SPECIAL YOUR METER APPLICATIONS Model LP4 USER S MANUAL Loop mA LOOP POWERED PROCESS METER SERIES SPECIAL 5137r01...

Страница 2: ...6 13 4Key UP fast access 7 13 5 Tools menu 7 14 Technical specifications 8 15 Error codes 8 16 Mechanical dimensions mm inch 8 17 Precautions on installation 9 18 Warranty 9 19 Factory default paramet...

Страница 3: ...d connections Inverted connections will not damage the instrument the loop will remain open and the instrument does not operate display does not light Terminal 2 is not connected Connecting any of the...

Страница 4: ...ries parameters and select configuration values Key SQ functions as the ENTER key It selects the menu entry currently displayed At numerical value entries it validates the number displayed Key UP 5 mo...

Страница 5: ...r appears and select by pressing the SQ key or wait without pressing any key until the automatic rollback activates When exiting the fast access menu the instrument returns to normal mode of operation...

Страница 6: ...ads wait while performs the reading of the actual input signal value and associates this value to the input low parameter When finished the instrument goes back to the Correction low F Lo menu entry a...

Страница 7: ...ect Measure function MEAS to activate an access to visualize the actual input signal value in milliamperes without the scaling 13 5 Tools menu The Tools tool menu groups several functions at the Input...

Страница 8: ...isplay display refresh 2 times second acquisition per second 2 acquisitions second memory retention values for maximum and minimum reading are stored every 10 minutes INPUT SIGNAL signals accepted 4 2...

Страница 9: ...r than the minimum current needed The instrument is designed to be panel mounted An appropriate ventilation of the instrument must be assured Do not expose the instrument to excess of humidity Maintai...

Страница 10: ...of LP4 loop powered meter placed close to the transmitter using the existing loop to the PLC 4 20mA transmitter Units LP4 loop powered meter PLC The LP4 loop powered meter can be directly inserted int...

Страница 11: ...2 3Protector KIP Wall mount housing Together with the KIP protector offers a full IP65 protection For for 96x48mm panel meters 22 2 4WME wall housing Benchtop housing for for 96x48mm panel meters Han...

Страница 12: ......

Отзывы: