FEMA ELECTRÓNICA . Series M . M60-P
6
1.10
Configuration menu
Press ‘SQ’ (
<
) for 3 seconds to access the ‘
configuration menu
’.
For a description on how to operate inside the menus see sec
-
tion
. For a full vision of the ‘
configuration menu
’ structure
.
To configure the initial set up of the instrument, select the input sig
-
nal range, the decimal point position, and scale the reading.
Access the ‘
Input
’ (‘
InP
’) menu to select the input signal range. Select
rear jumper at position ‘5’ (for mA), or ‘4’ (for Vdc and potentiom
-
eters)
• Select ‘
420
’ for 4/20mA
• Select ‘
010
’ for 0/10Vdc
• Select ‘
b20
’ for ±20mA
• Select ‘
b10
’ for ±10Vdc
• Select ‘
P-5K
’ for potentiometers with nominal value between 200
Ohms and 5 KOhms
• Select ‘
P-5M
’ for potentiometers with nominal value between
5KOhms and 5 MOhms. Then introduce the value of your potenti
-
ometer, in KOhms
• Select ‘
PSIV
’ to connect to a potentiometer that is already pow
-
ered from an external element. The meter will not generate exci
-
tation voltage but will read the excitation voltage provided to the
potentiometer.
Access the ‘
Decimal point
’ (‘
dP
’) menu to select the decimal point
position. Move the decimal point by pressing the ‘LE’ (
3
) key.
Scale the reading at the ‘
Scaling
’ (‘
ScAL
’) menu. There are four pa
-
rameters to configure :
• ‘
Input low
’ (‘
ILo
’) - minimum input signal, in mA, Vdc or % of the
potentiometer value, with two decimals.
• ‘
Display low
’ (‘
dLo
’) - reading associated to the minimum input signal.
• ‘
Input high
’ (‘
IhI
’) - maximum input signal, in mA, Vdc or % of the
potentiometer value, with two decimals.
• ‘
Display high
’ (‘
dhI
’) - reading associated to the maximum input signal.
The ‘
Field correction
’ (‘
F.cor
’) functions allows to correct the instrument
scaling parameters, when the instrument is being installed on the field,
providing a fast and easy way to compensate offset signals (only available
for process signals).
To operate the ‘
Field correction
’ (‘
F.cor
’) function for the offset correction,
generate the minimum input signal and access the ‘
Field low
’ (‘
F.Lo
’) func
-
tion. Then the following sequence will start
• message with signal type (‘
mA
’ or ‘
Vdc
’)
• message ‘
wait
’ (‘
WAIt
’) in flash mode
• after 5 seconds, message ‘
ok
’ (‘
oK
’) appears
• at this point, press key SQ (‘
<
‘)
• the menu returns to menu entry ‘
Field Low
’ (‘
F.Lo
’)
The instrument has read the input signal and automatically configures the
‘
Input low
’ (‘
I.Lo
’) for you.
Repeat the process generating the maximum input signal and access the
‘
Field high
’ (‘
F.hI
’) menu. The instrument will read the input signal and
automatically configure the ‘
Input high
’ (‘
I.hI
’) parameter to match the
signal read.
Application - a 0/10 Bar pressure transmitter provides a 4/20 mA output
signal. At installation, the operator detects that the reading at 0 Bar is
0.34 Bar and that at 10 Bar the reading is 10.72 Bar. Apply the ‘
Field cor-
rection
’ / ‘
F.Lo
’ function while reading is 0.34 Bar and the instrument will
automatically correct the reading to 0.00 Bar. Afterwards, apply the ‘
Field
correction
’ / ‘
F.Hi
’ function while reading is 10.72 Bar and the instrument
will automatically correct the reading to 10.00 Bar.
1.10.1 Initial set-up
1.10.2 Field correction
Field correction
Correction high
Correction low
Wait (5 sec.)
(
<
)
Wait (5 sec.)
(
<
)
Decimal point
Scaling
Input low
Display low
Input high
Display high
Range de 4/20 mA
Range de 0/10 Vdc
Range de ±20 mA
Range de ±10 Vdc
Input
Potentiometer (< 5 KOhms)
Potentiometer (< 5 MOhms)
Value in KOhms
Passive