background image

FEMA ELECTRÓNICA . Series M . M40-A

10

Tools

Key UP

 

(‘Fast access’)

Memory of 

maximum

Memory of 

minimum

Setpoint 1

Setpoint 2

Setpoint 3

‘Measure’

1.12 Configuration menu (cont.)

The ‘UP’ (

5

) key at the front of the instrument gives access to a list 

of functions configurable by the operator. See section 

1.10

 for an ex-

planation on how to operate the ‘

fast access

’ menu.

the ‘

Key UP (Fast access)

’ (‘

K.uP

’) menu allows to select which func-

tions will be accessible through the ‘fast access’ menu. Select ‘

on

’ to 

activate each function.

• the ‘

Setpoint

 

1

’ (‘

ALr1

’) function allows to visualize and modify the 

alarm

 

1 setpoint through the ‘fast access’ menu.

• the ‘

Setpoint

 

2

’ (‘

ALr2

’) function allows to visualize and modify the 

alarm

 

2 setpoint through the ‘fast access’ menu.

• the ‘

Setpoint

 

3

’ (‘

ALr3

’) function allows to visualize and modify the 

alarm

 

3 setpoint through the ‘fast access’ menu.

•  the    ‘

Memory of maximum

’ (‘

MAX

’)

 

or

 

Memory of minimum

’ 

(‘

MIn

’) functions allow to visualize the maximum or minimum read-

ing value stored in memory. To reset this value, visualize the memory 
value at the ‘fast access’ menu with key UP (

5

) and when message 

rSt

’ is displayed, press (

<

) to reset.

• the ‘

Measure

’ (‘

MEAS

’) function allows to visualize the actual sig-

nal at input terminals, without scaling. Example : with an instrument 
with input 0/10

 

Vac, and with reading scaled to 0/750.0, the ‘

mea-

sure

’ function will show the direct value in Vac, without the scaling.

1.12.5 Fast access

If only a single function is selected for the ‘fast access’ menu, press-
ing the the ‘UP’ (

5

) key will shortly display the function name and 

then automatically jump to the function value.

1.12.6 Super fast access

On power-up

Delay

Seconds

the ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 
not apply to instrument restart due to change in configuration.

• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds. The 

instrument waits the configured time before starting normal func-
tion. During this waiting time, the display shows all decimal points 
on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui-
sition and there is no communications or control being performed. 
After  the  configured  time  is  over,  the  instrument  starts  in  normal 
function. Delay value between 0 and 200 seconds.

Application - the start-up process for an automation system implies 
that different parts of the system (engines, actuators, controllers, ...) 
have different start-up times. The ‘Delay’ function gives time to the 
instrument to wait until the slowest part of the system is fully func

-

tional before executing actions on the system (signal reading, relay 
activation, ...)

1.12.7 Menu ‘On Power Up’

Содержание M40-A

Страница 1: ...48mm size 1 8 DIN Reading with 4 digit display Fast access to alarm setpoints on power up function measure function configurable reading brightness Universal AC and DC power Up to 3 optional modules for output and control relays analog outputs Modbus RTU communications RS 485 ASCII RS 232 www fema es Tel 34 93 729 6004 info fema es User s Manual ELECTRONICS FOR INDUSTRIAL AUTOMATION PANEL METERS S...

Страница 2: ...rs memory for maximum and minimum reading password protection 5 brightness levels 1 1 How to order M40 A Model Power Option1 Others H Option2 Option3 R1 1 relay AO analog output RTU Modbus RTU S4 RS 485 S2 RS 232 empty H 85 265Vac dc L 11 60Vdc 24Vac 48Vac NBT no buttons 65 front IP65 G green led Index 1 Panel meter M40 A 2 1 1 How to order 2 1 2 Front view 3 1 3 Rear view 3 1 4 Power connections ...

Страница 3: ...r see section 1 4 1 2 3 8 9 0 Detail of the plug in screw terminals provided with the instrument The instrument is provided with all terminals needed both male and female 1234 To configure the voltage AC measure select the jumper for the de sired scale as indicated in the table below Then activate the selected scale in the configuration menu see section 1 12 1 and connect the input signal to the s...

Страница 4: ...s 2 0KHz for AC currents minimum frequency 25Hz for reading oscillation 1 count 1 7 Technical specifications Power power H 85 a 265Vac dc power L 11 a 60Vdc y 24 48Vac isolation 2500Veff with power H 1500Veff with power L all units tested during 60 seconds consumption 1 5W only meter 4 0W meter with options Configuration 3 buttons front keypad and rear jumper Front protection IP54 standard IP65 op...

Страница 5: ... 12 4 Password configuration block 1 12 9 Measure yes 1 12 5 Peak Hold yes 1 12 4 Display brightness 5 levels 1 12 12 Table 4 Functions included 1 7 Technical specifications cont 44 92 Panel cut out 16 8 75 1 8 Mechanical dimensions mm 1 9 Coupling AC or AC DC The instrument provides and internal jumper to block the DC component of the signal By default the blocking of the DC com ponent is disable...

Страница 6: ... through the different menu op tions At menus with numerical value entries it modifies the digit selected by increasing its value to 0 1 2 3 4 5 6 7 8 9 Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the changed parameters are activated At menus with numer...

Страница 7: ...gnal and access the Field low F Lo function Then the following sequence will start message with signal type mA or Vdc message wait WAIt in flash mode after 5 seconds message ok oK appears at this point press key SQ the menu returns to menu entry Field Low F Lo The instrument has read the input signal and automatically config ures the Input low I Lo for you Repeat the process generating the maximum...

Страница 8: ...ays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set point value is passed Value from 0 0 to 99 9 seconds at Deactivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint value plus the hyste...

Страница 9: ...ixed Reading remains in the following format XXXX0 the Memory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see section 1 12 5 the Memory of minimum MAX function displays the minimum reading value stored in memory It also provides a way to reset the valu...

Страница 10: ...with an instrument with input 0 10Vac and with reading scaled to 0 750 0 the mea sure function will show the direct value in Vac without the scaling 1 12 5 Fast access If only a single function is selected for the fast access menu press ing the the UP 5 key will shortly display the function name and then automatically jump to the function value 1 12 6 Super fast access On power up Delay Seconds Th...

Страница 11: ...front leds With this function it is possible to adapt the instrument to the environment light intensity 1 12 9 Function Password 1 12 10 Factory reset Menus OPt 1 OPt 2 and OPt 3 give access to the configuration menus of the output and control modules installed at slots Opt 1 Opt 2 and Opt 3 See section 2 for a list of output and control modules available for each slot The configuration menu of ea...

Страница 12: ...ut high Display high Alarm1 Setpoint Hysteresis Setpoint2 Active Alarm type Activation delay Deactivation delay Left zeros Steps Average filters 0 0 to 99 9 Display Fixed digits Memory of maximum Memory of minimum Dummy zero Peak Hold Time seconds Alarm2 menu Alarm3 menu Relay inverted Locked alarm Scale 600Vac Scale 100Vac Scale 10Vac Scale 1Vac Scale 100mVac Scale 5Aac Scale 1Aac Field correctio...

Страница 13: ...int2 Setpoint3 Measure On power up Delay Seconds Option1 Configuration menu for the module installed at Opt 1 Option2 Configuration menu for the module installed at Opt 2 Option3 Configuration menu for the module installed at Opt 3 Password Firmware version Factory reset Minimum Brightness Maximum Standard Key LE Alarm unlock No function ...

Страница 14: ...ation for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock the lower clips marked with B and remove the front cover Let the inside of the instrument slide out of the housing To reinsert the instrument make sure that all modules are correctly connected to the...

Страница 15: ...ation of conformity This instrument is warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse accident or manipulation by non autho rized personnel In case of malfunction get in contact with your local provider to arrange for repair Within the warranty period and after examination by the manufacturer the unit will...

Страница 16: ...standalone for delayed installation as they do not require soldering or special configuration 2 Output and control modules 2 1 Module R1 2 2 Module AO Terminal A Common Terminal B NO Normally Open Terminal C NC Normally Closed Opt 2 Opt 1 Opt 3 Power A B C A B C A B C Signal The AO module provides 1 analog output with 4 20mA or 0 10Vdc configurable output range Output current loop configurable as ...

Страница 17: ...dule for M Series of panel meters ASCII protocol with Master Slave archi tecture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visible using hyperterminal or similar programs Configurable for direct retransmission to remote meter of M Series 14mm and 20mm digit height and BDF Series 60mm and 100mm digit height Access to display values...

Страница 18: ...patible with standard R1 modules The R2 R4 and R6 modules can be ordered pre installed into a M Series panel meter or standalone for delayed installation as they do not require soldering or special configuration The S2 module provides a RS 232 communications module for M Series of panel meters ASCII protocol with Master Slave archi tecture Addressable with up to 31 modules Frames codified in rep r...

Страница 19: ...FEMA ELECTRÓNICA Series M M40 A 19 T h i s p a g e b l a n k ...

Страница 20: ...m the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front IP65 protection with sealing of front filter clips opening the front filter removes the IP65 sealing permanently 3 Other options 3 1 Option NBT 3 2 Option 65 3 3 Option G ...

Страница 21: ...96mmfor96x48mm instruments Front IP65 protector for M Se ries panel meters Benchtop housing for M Series panel meters Handle with three selectable positions Power con nector with manual switch and fuse holder 4 Accessories 4 1 THM benchtop housing 4 2 Adapter KA96 4 3 Adapter DRA M 4 4 Protector KIP ...

Страница 22: ...FEMA ELECTRÓNICA Series M M40 A 22 Notes ...

Страница 23: ...FEMA ELECTRÓNICA Series M M40 A 23 Notes ...

Страница 24: ...3 info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instruments mA Vdc Pt100 Pt100 Pot Load Shunts X 1 X 5 RS 232 RS 485 BCD MODBUS Vac Vac TrueRMS Vdc TrueRMS Aac Aac Hz Custom Adc TC ...

Отзывы: