FEMA ELECTRÓNICA . Series K . K40-232
20
1.28 Configuration menu (cont.)
At the ‘
Password
’ (‘
PASS
’) menu select a 6 digit code to block access
to the ‘
configuration menu
’. Instrument configuration will not be ac
-
cessible to non authorized personnel. To activate the ‘
Password
’ se
-
lect ‘
on
’ and introduce the code.
The code will be requested when trying to access the ‘
configuration
menu
’ (key ‘SQ’ (
<
)). The ‘
fast access
’ menu is not password pro
-
tected.
The ‘
Version
’ (‘
VEr
’) menu informs of the current firmware version
installed in the module.
At the ‘
Brightness
’ (‘
LIGh
’) menu select the light intensity for the
front leds. With this function it is possible to adapt the instrument to
the environment light intensity.
1.28.11
Menu ‘Key LE’
Menus ‘
OPt.1
’, ‘
OPt.2
’ and ‘
OPt.3
’ give access to the ‘
configuration
menus
’ of the output and control modules installed at slots Opt.1,
Opt.2 and Opt.3.
See section
for a list of output and control modules available for
each slot. The ‘
configuration menu
’ of each module is described at
the User’s Manual of each module.
1.28.12
Function ‘Password’
At the ‘
Factory reset
’ (‘
FAct
’) menu, select ‘
yes
’ to load the default
factory configuration for the instrument
1.28.13 Factory reset
1.28.14
Firmware version
1.28.15
Brightness
The ‘LE’ (
3
) key at the front of the instrument can be configured to
activate several functions. Only one function can be assigned to the
‘LE’ (
3
) key
• the ‘
No function
’ (‘
nonE
’)
value assigns no function.
• the ‘
Alarm unlock
’ (‘
A.Lck
’)
value assigns the manual unlock of the
alarms function, for instruments with the ‘
Locked alarms
’ (‘
A.Lck
’)
function activated
1.28.10
Menu ‘Save to E2PROM’
Key ‘LE’
Alarm unlock
no function
Option
1
Configuration menu for the module installed at Opt.1
Option
2
Configuration menu for the module installed at Opt.2
Option
3
Configuration menu for the module installed at Opt.3
Password
Version
Factory reset
Minimum
Brightness
Maximum
Standard
By default, saving values to the E2PROM from the communciations
bus, is disabled. Select ‘on’ to save updates on the setpoint values
also to the E2PROM
This parameter is set to ‘oFF’ by default because E2PROM memo
-
ries have a typical live of 100.000 saving cycles. This value is clearly
enough for manual changes on the setpoint, but from a communica
-
tions bus, this value can be achieved very fast if the sender is not
accurate enough in controlling the send frames.
1.28.16 Access to optional modules
Remote
SAve to E2PROM