1 Safety
advisories
When starting up and operating the controller, the following important safety advisories as well as
the installation and wiring notes must be strictly observed:
-
All installation, startup and maintenance work must be performed only by qualified specialists. In particular the
following regulations must be observed : VDE0100, EN 50110 (VDE0105), EN 60204 (VDE0113), EN 50178
(VDE0160), EN 60335 (VDE0700), fire protection codes, accident prevention regulations as well as the relevant
regulations for industrial doors (ZH1/494, EN12453, EN12978)
-
The controller may be opened only if the supply voltage has been switched off completely.
-
If the potential free contacts of the output relays or other terminals are supplied by a foreign voltage witch are
still present after switching off the controller, you must install a sign on the housing that says: “ATTENTION!
You must disconnect all supply circuits before opening the housing”.
-
The controller must never be operated while open.
-
The controller must never be operated without the CEE-plug except that a main switch is installed.
The main switch and the CEE-plug must be within easy reach.
-
If the connecting lead is damaged, it must be changed by the manufacturer or another qualified person.
-
Hazardous voltages remain stored in the intermediate circuit capacitors for up to five minutes after power has
been turned off. The discharge time until voltages fall below 60VDC is a maximum of 5 minutes. Touching
internal controller components within this discharge time is hazardous.
-
A defective switching power supply can considerably increase the discharge time of the intermediate circuit
capacitors down to a voltage of less than 60VDC. Here discharge times of up to 10 minutes may be possible.
-
In case the 24V controller voltage is short circuited or overloaded, the switching power supply will not start up
even though the intermediate circuit capacitors are charged. The display and LED’s remain off. The power
supply can be restarted only after eliminating the short circuit or extreme overload.
-
After turning off the supply, the power supply is still fed from the intermediate circuit capacitors for several
seconds and maintains the supply function for a certain time depending on the power supply load.
-
The processor circuit with 7-segment display, EPROM and multiplexers is galvanically directly connected to the
mains supply. Note this when making any checking measurements (for measurements in the processor circuit,
do not use test equipment with PE reference to the measuring circuit).
-
It is not permitted to operate the controller without a connected protection earth. The absence of a protection
earth will result in hazardous voltages on the controller housing caused by drain capacitors. The protection earth
should be connected in compliance with EN50178 Section 5.2.11.1 for drain currents >3.5mA.
-
Turning on or operating the controller in the presence of condensation is not permitted and may result in
permanent damage.
-
If controllers are used outside the specified temperature range, a regulated and monitored climate controller
system must be in place to ensure that the specified working temperature range is maintained when turning on
the supply and when operating the controller.
-
The controller must never be operated with a damaged membrane keypad or sight glass. Damaged keypads
and windows must be replaced. To prevent damage to the keypad, do not use pointed objects to actuate the
keys. The keypad is designed for finger operation only.
-
Before tuning on the controller voltage for the first time, ensure that the processor cards (plug-in modules) are in
the correct position. Incorrect fit of the cards can result in damage to the controller, likewise the installation of
non-approved third-party equipment.
-
When moving the door in deadman mode, ensure that the door area can be inspected by the operator, since in
this mode safety equipment such as safety bar and light barrier are defeated.
-
Parameter settings and the function of the saftey devices have to be checked before operating the door.
Parameter settings and wire bridges are only allowed to set by an instructed person.
WARNING Failure to observe the safety advisories can result in physical harm or damage to the
controller.
These safety advisories make no claim to completeness. If you have questions about the product, contact
your vendor.
The manufacturer has carefully checked and inspected the device hardware and software, but no warranty is
given for a complete absence of errors.
A device mark (nameplate with name and address of the manufacturer, serial number, model number, supply
voltage and temperature range) must be applied by the user.