FU3E_Inbetriebnahme_7_GB.doc
6. Set upper pre-limit switch so that it just trips.
7. Press
¿
OPEN-key to bring door to approx. 10cm from the opened position.
IMPORTANT
The distance depends greatly on the door type and the speed; increase this value
for fast moving doors.
8. Set upper pre-limit switch so that it just trips
IMPORTANT Do not travel past the limit switch in the end positions!
9. If necessitated by door type: set upper and lower EMERGENCY limit switches
Connect normally closed contacts, e.g., in the safety circuit, in series with thermopile detector.
10. Press
Å
STOP and
¿
OPEN to enter parameterizing mode and select Parameter P.980 „Service
Mode“, open and set parameter value „2“ to „0“ (Automatic mode).
11. Correct limit switch positions for Door OPEN and Door CLOSE as needed by fine adjustment of the end
positions in automatic mode.
WARNING
To prevent unintended moving of the door, adjust the limit switches only when the
Emergency-STOP is activated or with the controller turned off !
12. The door may now be operated in Automatic mode.
7.3 New request for teaching end positions
If the end positions have been pre-taught (using electronic limit switches) but these are not appropriate for
the door in question, teaching the end positions can be newly requested.
Here the following parameter must be set:
P.210: 5 = New teaching of all end positions
7.4 Boost / Increasing power at slow speeds
Boost is used to increase the power of the drives in the lower speed range. Too much or too little boost can
result in improper door operation. The adjustment range for boost is 0-30%. If too much boost is already set,
this will result in a overcurrent fault (F.510/F.410). In this case the boost must be reduced.
If the boost is low or 0 and the motor still does not have sufficient force to move the door, the boost must be
increased.
Due to the large number of possible door types, the correct setting for boost should be empirically
determined.
1. Open parameterizing mode by pressing
Å
STOP and
¿
OPEN at the same time.
2. Open Boost parameter by pressing the
¿
À
arrow keys. Boost can be set separately for OPEN and
CLOSE.
Boost for Open: P.140.
Boost for Close: P.145
3. Open parameter by pressing
Å
STOP and use the
¿
À
arrow keys to change it in small steps of max.
5, then save by pressing
Å
STOP (long).
4. After changing the boost, exit parameterizing mode by long pressing of the
Å
STOP key and test the
setting in run mode.
)
You can use diagnostic parameter P.910 = 2 to display the motor current. The boost should be set so
that the motor current remains as low as possible.