CAUTION:
•
The relay outputs are designed for max. 24 V DC / 2 A continuous load.
•
The maximum switching current must not exceed 1 A.
•
The relay outputs are intended for switching resistive loads only. In case an inductive load is
connected, the relay contacts must be protected by an external protective circuit.
5.6 Digital Inputs on Connector X5
There are 2 digital inputs available on X5. The optocouplers on X5 are galvanically isolated from the reader
electronics and must therefore be supplied with an external voltage.
Pin Number at
Connector X5
Pin Assignment
1
OPTO2-IN –
2
OPTO2-IN +
3
OPTO1-IN –
4
OPTO1-IN +
Table 9: Pin Assignment X5 (digital inputs)
Fig. 14: Connector X5 pin assignment for digital inputs
Fig. 15: External wiring of the digital inputs